General information

Part 1

Section 1.2

Installation basics

Introduction

Information in this section is provided so that the service technician will have a basic knowledge of installation requirements for home standby systems. Problems that arise are often related to poor or unau- thorized installation practices.

A typical home standby electric system is shown in Figure 1 (next page). Installation of such a system includes the following:

Selecting a Location

Grounding the generator.

Providing a fuel supply.

Mounting the load center.

Connecting power source and load lines.

Connecting system control wiring.

Post installation tests and adjustments.

Selecting A Location

Install the generator set as close as possible to the electrical load distribution panel(s) that will be pow- ered by the unit, ensuring that there is proper ventila- tion for cooling air and exhaust gases. This will reduce wiring and conduit lengths. Wiring and conduit not only add to the cost of the installation, but excessively long wiring runs can result in a voltage drop.

Control system interconnections between the transfer switch and generator consist of N1 and N2, and leads 23, 15B and 0. Control system interconnection leads must be run in a conduit that is separate from the AC power leads. Recommended wire gauge size depends on the length of the wire:

Max. Cable Length

Recommended Wire Size

 

 

35 feet (10.67m)

No. 16 AWG.

 

 

60 feet (I8.29m)

No. 14 AWG.

 

 

90 feet (27.43m)

No. 12 AWG.

 

 

LP (propane) gas is usually supplied as a liquid in pressure tanks. Both the air-cooled and the liquid cooled units require a “vapor withdrawal” type of fuel supply system when LP (propane) gas is used. The vapor withdrawal system utilizes the gaseous fuel vapors that form at the top of the supply tank.

The pressure at which LP gas is delivered to the generator fuel solenoid valve may vary considerably, depending on ambient temperatures. In cold weather, supply pressures may drop to “zero”. In warm weath- er, extremely high gas pressures may be encountered. A primary regulator is required to maintain correct gas supply pressures.

Current recommended gaseous fuel pressure at the inlet side of the generator fuel solenoid valve is as follows:

 

LP

NG

Minimum water column

10 inches

5 inches

Maximum water column

12 inches

7 inches

A primary regulator is required to ensure that proper fuel supply pressures are maintained.

*DANGER: LP AND NATURAL GAS ARE BOTH HIGHLY EXPLOSIVE. GASEOUS FUEL LINES MUST BE PROPERLY PURGED AND TESTED FOR LEAKS BEFORE THIS EQUIPMENT IS PLACED INTO SERVICE AND PERIODICALLY THEREAFTER. PROCEDURES USED IN GASEOUS FUEL LEAKAGE TESTS MUST COMPLY STRICTLY WITH APPLICABLE FUEL GAS CODES. DO NOT USE FLAME OR ANY SOURCE OF HEAT TO TEST FOR GAS LEAKS. NO GAS LEAKAGE IS PERMITTED. LP GAS IS HEAVIER THAN AIR AND TENDS TO SETTLE IN LOW AREAS. NATURAL GAS IS LIGHTER THAN AIR AND TENDS TO SETTLE IN HIGH PLACES. EVEN THE SLIGHTEST SPARK CAN IGNITE THESE FUELS AND CAUSE AN EXPLOSION.

Grounding The Generator

The National Electric Code requires that the frame and external electrically conductive parts of the gen- erator be property connected to an approved earth ground. Local electrical codes may also require prop- er grounding of the unit. For that purpose, a ground- ing lug is attached to the unit. Grounding may be accomplished by attaching a stranded copper wire of the proper size to the generator grounding lug and to an earth-driven copper or brass grounding-rod (elec- trode). Consult with a local electrician for grounding requirements in your area.

The Fuel Supply

Units with air-cooled engines were operated, tested and adjusted at the factory using natural gas as a fuel. These air-cooled engine units can be converted to use LP (propane) gas by making a few adjustments for best operation and power.

Use of a flexible length of hose between the genera- tor fuel line connection and rigid fuel lines is required. This will help prevent line breakage that might be caused by vibration or if the generator shifts or settles. The flexible fuel line must be approved for use with gaseous fuels.

Flexible fuel line should be kept as straight as possi- ble between connections. The bend radius for flexible fuel line is nine (9) inches. Exceeding the bend radius can cause the fittings to crack.

The Transfer Switch / Load Center

A transfer switch is required by electrical code, to pre- vent electrical feedback between the utility and stand- by power sources, and to transfer electrical loads from one power supply to another safely.

Transfer Switches:

Instructions and information on transfer switches may be found in Part 3 of this manual.

Page 11

Page 13
Image 13
Generac Power Systems 9 kW NG, 10 kW LP Installation basics, Selecting a Location, Grounding The Generator, Fuel Supply