DC control

Part 4

Section 4.2

Operational analysis

When the circuit board’s “engine warm-up timer” times out, circuit board action completes the Wire 23 circuit to ground. The transfer relay then energizes and its normally open contacts close.

Standby power is now delivered to the standby closing coil (C2), via Wires E1/E2, the normally open transfer relay contacts, Wire 205, limit switch XB1, Wire B, and a bridge rectifier. The standby closing coil energizes and the main current carrying contacts of the transfer switch are actuated to their STANDBY source side.

As the main contacts move to their STANDBY source side, a mechanical interlock actuates limit switch XB1 to its open position and limit switch XA1 to its “Utility” side position. When XB1 opens, standby closing coil C2 3 de-energizes.

Standby power is delivered to the LOAD terminals (T1/T2) of the transfer switch.

Figure 5. Circuit Condition - Initial Transfer to Standby

CB

CONTROLLER DISPLAY

Running - Utility Lost

44

11

33

22

00

240VAC GENERATOR OUTPUT

NEUTRAL

 

N1

240 VAC

 

 

 

 

UTILITY

 

 

INPUT

OPTIONAL

 

 

BATTERY WARMER

N1

N2

 

 

 

 

CONTROLLER

 

 

 

 

 

 

 

 

 

PRINTED CIRCUIT BOARD

 

N1

N2

 

 

 

85

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

86

2

J1

 

 

 

 

 

 

 

 

 

 

 

 

 

TO

13

3

 

 

 

 

 

 

 

 

7.5 AMP FUSE

 

 

 

 

 

 

 

 

 

 

 

PCB

18

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GOVERNOR

 

J3

 

 

 

 

 

 

SELF RESETTING FUSE

ACTUATOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J2

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

9

10

11

12

13 14

15

16

17 18

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

0

14

 

23

 

 

15B

 

0

56

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

820

 

 

14

 

 

 

 

 

 

 

 

 

 

 

817

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

818

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CS

 

 

FS

 

 

 

 

 

 

 

 

 

 

 

819

90

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BA - BRUSH ASSEMBLY

 

 

 

 

 

 

LOP - LOW OIL PRESSURE SWITCH

CB - CIRCUIT BREAKER, MAIN OUTPUT

 

 

 

SC - STARTER CONTACTOR

 

CS - CHOKE SOLENOID

 

 

 

 

 

 

SCR - STARTER CONTROL RELAY

FS - FUEL SOLENOID

 

 

 

 

 

 

SM - STARTER MOTOR

 

 

 

HTO - HIGH TEMPERATURE SWITCH

 

 

 

 

 

SP_ - SPARK PLUG

 

 

 

IM_ - IGNITION MODULE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED BOARD

820

1

L1

817

2

L2

818

3

 

819

4

 

0 GROUND

15B

+ BATTERY

23 TRANSFER

=12 VDC ALWAYS PRESENT

=AC VOLTAGE

=GROUND FOR CONTROL PURPOSES

=12 VDC DURING CRANKING ONLY

=12 VDC DURING ENGINE RUN CONDITION

=DC FIELD EXCITATION

=5 VDC TO LED