Generac Power Systems 16 kW NG, 10 kW LP, 13 kW NG, 7 kW NG, 9 kW NG, 8 kW LP manual KW Choke Solenoid

Models: 18 kW NG 14 kW LP 16 kW NG 20 kW LP 17 kW LP 8 kW LP 9 kW NG 7 kW NG 13 kW NG 10 kW LP

1 192
Download 192 pages 31.78 Kb
Page 137
Image 137

DC control

Part 4

Section 4.4

Diagnostic tests

CHOKE VALVE IN OPEN POSITION

CHOKE SOLENOID

AIR BOX

CHOKE VALVE IN CLOSED POSITION

Figure 26. 8kW Choke Solenoid

Figure 28. Checking Ignition Spark

To determine if an engine miss is ignition related, connect the spark tester in series with the spark plug wire and the spark plug (Figure 29). Then, crank and

Figure 27. Spark Testerstart the engine. A spark miss will be readily apparent. If spark jumps the spark tester gap regularly but the engine miss continues, the problem is in the spark plug or in the fuel system.

NOTE: A sheared flywheel key may change ignition timing but sparking will still occur across the spark tester gap.