Section 4.2

Operational analysis

Part 4

DC control

Utility Voltage Dropout and Engine Cranking

After ten (10) seconds and when the circuit board’s 10-second timer has timed out, if utility voltage is still below

65 percent of nominal, circuit board action will energize the circuit board’s crank and run relays simultaneously.

Printed circuit board action delivers 12 volts DC to a starter contactor relay (SCR), via Wire 56. When the SCR energizes, its contacts close and battery power is delivered to a starter contactor (SC). When the SC energizes, its contacts close and battery power is delivered to the starter motor (SM). The engine cranks.

 

 