DC control

Part 4

Section 4.2

Operational analysis

The “engine warm-up timer” will run for about 5 seconds. When this timer finishes timing, board action will initiate transfer to the STANDBY power source. As shown in Figure 4 (below), the timer is still running and transfer has not yet occurred.

Generator AC output is available to transfer switch Terminal Lugs E1/E2 and to the normally open contacts of a transfer relay. However, the transfer relay is de-energized and its contacts are open.

Figure 4. Circuit Condition - Engine Startup and Running

CB

CONTROLLER DISPLAY

Running - Utility Lost

44

11

33

22

00

240VAC GENERATOR OUTPUT

NEUTRAL

 

N1

240 VAC

 

 

 

 

UTILITY

 

 

INPUT

OPTIONAL

 

 

BATTERY WARMER

N1

N2

 

 

 

 

CONTROLLER

 

 

 

 

 

 

 

 

 

PRINTED CIRCUIT BOARD

 

N1

N2

 

 

 

85

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

86

2

J1

 

 

 

 

 

 

 

 

 

 

 

 

 

TO

13

3

 

 

 

 

 

 

 

 

7.5 AMP FUSE

 

 

 

 

 

 

 

 

 

 

 

PCB

18

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GOVERNOR

 

J3

 

 

 

 

 

 

SELF RESETTING FUSE

ACTUATOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J2

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

9

10

11

12

13 14

15

16

17 18

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

0

14

 

23

 

 

15B

 

0

56

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

820

 

 

14

 

 

 

 

 

 

 

 

 

 

 

817

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

818

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CS

 

 

FS

 

 

 

 

 

 

 

 

 

 

 

819

90

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BA - BRUSH ASSEMBLY

 

 

 

 

 

 

LOP - LOW OIL PRESSURE SWITCH

CB - CIRCUIT BREAKER, MAIN OUTPUT

 

 

 

SC - STARTER CONTACTOR

 

CS - CHOKE SOLENOID

 

 

 

 

 

 

SCR - STARTER CONTROL RELAY

FS - FUEL SOLENOID

 

 

 

 

 

 

SM - STARTER MOTOR

 

 

 

HTO - HIGH TEMPERATURE SWITCH

 

 

 

 

 

SP_ - SPARK PLUG

 

 

 

IM_ - IGNITION MODULE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED BOARD

820

1

L1

817

2

L2

818

3

 

819

4

 

0 GROUND

15B

+ BATTERY

23 TRANSFER

=12 VDC ALWAYS PRESENT

=AC VOLTAGE

=GROUND FOR CONTROL PURPOSES

=12 VDC DURING CRANKING ONLY

=12 VDC DURING ENGINE RUN CONDITION

=DC FIELD EXCITATION

=5 VDC TO LED

Page 111

Page 113
Image 113
Generac Power Systems 9 kW NG, 10 kW LP, 13 kW NG, 7 kW NG, 8 kW LP, 17 kW LP Circuit Condition Engine Startup and Running