General information

Part 1

Section 1.4

Preparation before use

in the selector knob and pull out to overcome spring pressure and then twist clockwise 90 degrees and allow the selector to return in once aligned with the LP (Liquid Propane) position.

6.Save this tool with the Owner's Manual.

7.Install the battery, door and close the roof.

8.Reverse the procedure to convert back to natural gas.

Figure 1. Demand Regulator

10, 12, 14, 16, 17 And 20 kW, V-twin Engines:

To reconfigure the fuel system from NG to LP, follow these steps:

NOTE: The primary regulator for the propane sup- ply is NOT INCLUDED with the generator. A fuel pressure of 10 to 12 inches of water column (0.36 to 0.43 psi) to the fuel inlet of the generator MUST BE SUPPLIED.

FUEL SELECTION LEVER -

“IN” POSITION FOR NATURAL GAS

Figure 2. 10 kW, GT-530 (Inlet Hose Slid Back)

FUEL SELECTION LEVER -

“OUT” POSITION FOR LIQUID PROPANE (VAPOR) FUEL

Figure 3. 10 kW, GT-530 (Inlet Hose Slid Back)

1.Open the roof.

2.For 10 kW units: Loosen clamp and slide back the air inlet hose.

Slide fuel selector on carburetor out towards the back of the enclosure (Figures 2 and 3).

Return the inlet hose and tighten clamp securely.

For 12, 14, 16, 17 and 20 kW units: remove the air cleaner cover.

Slide the selector lever out towards the back of the enclosure (Figures 4 and 5).

Return the air cleaner cover and tighten the two thumb screws.

3.Close the roof.

4.Reverse the procedure to convert back to natural gas.

FUEL SELECTION LEVER -

“IN” POSITION FOR NATURAL GAS

Figure 4. 12/14/16/17/20 kW, GT-990/GT-999

(Airbox Cover Removed)