DC control

Part 4

Section 4.3

Troubleshooting flow charts

Problem 17 – Engine Cranks but Won’t Start

TEST 66 – CHECK

 

 

 

GOOD

FUEL SUPPLY AND

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAD

 

 

 

 

 

 

 

 

 

TEST 67 – CHECK CIRCUIT BOARD WIRE 14 OUTPUT

BAD

 

 

 

TEST 68 – CHECK

 

 

 

GOOD

 

 

 

 

 

 

 

 

FUEL SOLENOID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REPLACE FUEL SOLENOID

GOOD

 

 

 

 

FIND AND CORRECT

CAUSE OF NO FUEL

OR LOW PRESSURE

GOOD

CHECK AIR FILTER -

REPLACE AS NEEDED

REPLACE CIRCUIT BOARD

 

TEST 16 – CHECK

 

 

 

 

V-TWIN UNITS

GOOD

 

STEPPER MOTOR

 

 

 

 

 

 

CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAD

 

 

 

 

 

 

 

 

 

 

 

 

REPAIR OR REPLACE

SINGLE CYLINDER UNITS

TEST 69 – CHECK CHOKE SOLENOID

BAD

REPLACE CHOKE

SOLENOID

TEST 70 –

CHECK FOR

IGNITION

SPARK

BAD

GOOD

TEST 71 –

CHECK SPARK

PLUGS

BAD

CLEAN,

REGAP OR

REPLACE

 

 

 

TEST 77 –

 

 

GOOD

 

 

 

 

 

 

 

 

 

 

CHECK AND

 

GOOD

 

 

 

 

 

ADJUST VALVES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAD

READJUST

CHECK

FLYWHEEL GOOD

KEY

TEST 72 –

CHECK ENGINE

COMPRESSION

GOOD BAD

REPLACE FUEL

REGULATOR

TEST 73 – CHECK SHUTDOWN WIRE

BAD

REPAIR OR

REPLACE SHORTED WIRE 18 OR CIRCUIT BOARD

GOOD

TEST 74 – CHECK

IGNITION

MAGNETOS

 

BAD

 

 

 

 

 

REFER TO ENGINE

 

 

 

 

ADJUST OR

REPLACE

SERVICE MANUAL

Page 119

Page 121
Image 121
Generac Power Systems 13 kW NG, 10 kW LP, 7 kW NG Troubleshooting flow charts, Problem 17 Engine Cranks but Won’t Start