General information

Part 1

Section 1.3

Non-Prepackaged Interconnections

Connect a 2008 and later load center switch

to a Pre-2008 air-cooled generator.

Procedure:

1.Follow all instructions located in the Installation Manual that was supplied with the unit regarding mounting of the switch, junction box, and generator.

Note: When installing a standalone pre-2008 gen- erator, the battery charger will be located in the generator utilizing the 12 VDC trickle charger.

2.Inside the Junction box between the generator and the transfer switch there will be 4 wires coming from the generator and 5 wires from the transfer switch.

3.Using the following diagram and UL approved wire nuts connect the following wires together. Wire 0 will not be utilized for this setup.

Note: Remove the battery charger from the trans- fer switch; it will not be utilized in the operation of the generator.

PRE “08” HSB AIR-COOLED GENERATORS

SINGLE & V-TWIN ENGINES

CONTROL WIRES FROM ENGINE GENERATOR

CONTROL WIRES FROM

ENGINE GENERATOR

N1 (BLU) N1 (YEL)

N2 (YEL) N2 (YEL)

23 (BRN) 23 (WHT)

194 (ORG) 15B (RED)

 

0 (BLK)

WIRE NUTS

CONTROL WIRES FROM

TRANSFER SWITCH

 

Figure 3. Wire Connections

“08” & LATER LOAD CENTER

TRANSFER SWITCH

WIRE

 

NUTS

CONTROL WIRES FROM TRANSFER SWITCH

 

N1

(BLU)

N1 (YEL)

N2

(YEL)

N2 (YEL)

23 (BRN)

23 (WHT)

194

(ORG)

15B (RED)

 

 

0 (BLK)

EXTERNAL CUSTOMER

CONNECTION BOX

Figure 4. Pre-2008 HSB Interconnections

Page 15

Page 17
Image 17
Generac Power Systems 16 kW NG Non-Prepackaged Interconnections, PRE 08 HSB AIR-COOLED Generators Single & V-TWIN Engines