Section 3.3

Troubleshooting flow charts

Part 3

Transfer switch

Introduction To Troubleshooting

The first step in troubleshooting is to correctly identify the problem. Once that is done, the cause of the an be found by performing the tests in the appropriate flow chart.

Test numbers assigned in the flow charts are identical to test numbers in Section 3.4, “Diagnostic Tests.” Section 3.4 provides detailed instructions for performance of each test.

Problem 7 – In Automatic Mode, No Transfer to Standby

TEST 26 – CHECK

VOLTAGE AT

TERMINAL LUGS

E1 & E2

BAD

 

FIND CAUSE OF NO AC OUTPUT TO

 

 

 

TRANSFER SWITCH FROM GENERATOR

 

 

GOOD

TEST 27 – CHECK

MANUAL TRANSFER SWITCH OPERATION

GOOD

TEST 28 – CHECK #23

AND #15B WIRING

CONNECTIONS

BAD REPAIR OR REPLACE MECHANISM

BAD REPAIR OR REPLACE AS NEEDED

GOOD

TEST 29 – TEST

TRANSFER

RELAY

GOOD

TEST 30 – CHECK

STANDBY CONTROL

CIRCUIT

BAD REPLACE

BAD REPAIR AS NEEDED

Page 70

Page 72
Image 72
Generac Power Systems 7 kW NG, 10 kW LP, 13 kW NG, 9 kW NG Troubleshooting flow charts Part, Introduction To Troubleshooting