Generac Power Systems 9 kW NG, 10 kW LP, 13 kW NG and 20 kW Printed Circuit Board and J1 Connector

Models: 18 kW NG 14 kW LP 16 kW NG 20 kW LP 17 kW LP 8 kW LP 9 kW NG 7 kW NG 13 kW NG 10 kW LP

1 192
Download 192 pages 31.78 Kb
Page 103
Image 103

DC control

Part 4

Section 4.1

Description and components

18 17 16 15 14 13 12 11 10

4

3

9

8

7

6

5

4

3

2

1

2

1

J2 J1

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

J2 CONNECTOR

(PCB END)

4

3

2

1

J1 CONNECTOR

(PCB END)

J3

(STEPPER MOTOR)

3

4

10

11

12

13

14

15

16

17

18

1

2

1

2

3

4

5

6

7

8

9

J1 CONNECTOR

 

 

J2 CONNECTOR

 

 

(HARNESS END)

 

 

(HARNESS END)

 

 

1

2

REMOTE WIRELESS CONNECTION

N1/N2 CONNECTOR

N1/N2 CONNECTOR

(PCB END)

(HARNESS END)

 

Figure 7. 16, 17 and 20 kW Printed Circuit Board and J1 Connector

16, 17 and 20 kW J1 Connector Pin Descriptions

PIN

WIRE

CIRCUIT FUNCTION

 

 

 

J1-1

85

High temperature shutdown:

 

 

Shutdown occurs when Wire 85 is

 

 

grounded by contact closure in HTO

 

 

 

J1-2

86

Low oil pressure shutdown: Shutdown

 

 

occurs when Wire 86 is grounded by

 

 

loss of oil pressure to the LOP

 

 

 

J1-3

13

12 VDC source voltage for the circuit

 

 

board

 

 

 

J1-4

18

Ignition Shutdown: Circuit board

 

 

action grounds Wire 18 for ignition

 

 

shutdown.

 

 

 

J2-1

 

INTERNAL USE ONLY

 

 

 

J2-2

 

INTERNAL USE ONLY

 

 

 

J2-3

14

12VDC output for engine run condi-

 

 

tion. Used for fuel solenoid and choke

 

 

solenoid operation.

 

 

 

J2-4

817

Grounded by printed circuit board to

 

 

turn on System Ready (Green) LED.

 

 

 

J2-5

23

Switched to ground for transfer relay

 

 

operation

 

 

 

J2-6

 

NOT USED

 

 

 

J2-7

 

NOT USED

 

 

 

PIN

WIRE

CIRCUIT FUNCTION

 

 

 

J2-8

15B

Provides an electrical connection for

 

 

charge current to reach the battery

 

 

from the battery charger. Provides 12

 

 

VDC to the Transfer Relay

 

 

 

J2-9

820

Positive voltage (+5 VDC) for status

 

 

LEDs.

 

 

 

J2-10

0

Common Ground

 

 

 

J2-11

56

12 VDC output to starter contactor

 

 

relay for V-Twin engines

 

 

 

J2-12

4

Field Boost output

 

 

 

J2-13

818

Grounded by board to turn on the

 

 

Alarm (Red) LED.

 

 

 

J2-14

819

Grounded by board to turn on the

 

 

Maintenance Required (Yellow) LED.

 

 

 

J2-15

90

Switched to ground for choke sole-

 

 

noid operation

 

 

 

J2-16

 

INTERNAL USE ONLY

 

 

 

J2-17

 

NOT USED

 

 

 

J2-18

 

NOT USED

 

 

 

J3

 

Control wires for Stepper Motor

 

 

 

Wired Plug-1

N1

240 VAC sensing for control board.

 

 

 

Wired Plug-2

N2

240 VAC sensing for control board.

 

 

 

Page 101

Page 103
Image 103
Generac Power Systems 9 kW NG, 10 kW LP, 13 kW NG, 7 kW NG, 8 kW LP, 17 kW LP and 20 kW Printed Circuit Board and J1 Connector