AC generators

Part 2

Section 2.2 Operational analysis

Rotor Residual Magnetism

The generator revolving field (rotor) may be consid- ered to be a permanent magnet. Some “residual” magnetism is always present in the rotor. This residual magnetism is sufficient to induce a voltage into the stator AC power windings that is approximately 2-12 volts AC.

Field Boost (12-20 KW)

Field Boost Circuit:

When the engine is cranking, direct current flow is delivered from a circuit board to the generator rotor windings, via Wire 4.

The field boost system is shown schematically in Figure 2. Manual and automatic engine cranking is initiated by circuit board action, when that circuit board energizes a crank relay. Battery voltage is then delivered to field boost Wire 4 (and to the rotor), via a field boost resistor and diode. The crank relay, field boost resistor and diode are all located on the circuit board.

Notice that field boost current is available only while the crank relay is energized, i.e., while the engine is cranking.

 

TO LOAD

MLB = MAIN LINE

MLB

CIRCUIT BREAKER

 

STATOR

STATOR

POWER

POWER

WINDING

WINDING

Field boost voltage is reduced from that of battery voltage by the resistor action and, when read with a DC voltmeter, will be approximately 9 or 10 volts DC.

+12 VDC

 

 

 

 

PIN 5

13

 

 

 

 

 

 

56

TO

 

 

STARTER

 

FIELD

 

 

 

 

 

BOOST

 

 

DIODE

RESISTOR

 

 

 

 

 

 

PIN 1

 

 

CRANk

FIELD

4

STARTER

RELAY k1

CONTACTOR

BOOST

 

BASE

DIODE

 

 

TRANSISTOR

 

 

 

 

 

FIELD

 

 

 

BOOST

 

CIRCUIT BOARD

TO

 

 

 

ROTOR

 

Figure 2. Field Boost Circuit Schematic

TO LOAD

MLB MLB = MAIN LINE CIRCUIT BREAKER

SENSING

 

MAGNETIC

 

 

FIELD

 

ENGINE -

 

 

DIRECT

ROTOR

 

DRIVE

 

 

 

 

ENGINE -

 

MAGNETIC

DIRECT

 

FIELD

DRIVE

 

STATOR

 

 

EXCITATION

 

 

WINDING

 

STATOR

STATOR

POWER

POWER

WINDING

WINDING

MAGNETIC

FIELD

ROTOR

MAGNETIC

FIELD

FIELD BOOST FROM

CONTROL LOGIC

CIRCUIT BOARD

VOLTAGE

REGULATOR

CAPACITOR

STATOR

EXCITATION

WINDING

8/10 kW Units

12-20 kW Units

Figure 1. Operating Diagram of AC Generator

Page 35

Page 37
Image 37
Generac Power Systems 16 kW NG, 10 kW LP, 13 kW NG, 7 kW NG, 9 kW NG, 8 kW LP Rotor Residual Magnetism, Field Boost 12-20 KW