Generac Power Systems 9 kW NG, 7 kW NG Troubleshooting flow charts, Problem 9 Blown F1 or F2 Fuse

Models: 18 kW NG 14 kW LP 16 kW NG 20 kW LP 17 kW LP 8 kW LP 9 kW NG 7 kW NG 13 kW NG 10 kW LP

1 192
Download 192 pages 31.78 Kb
Page 73
Image 73

Transfer switch

Part 3

Section 3.3

Troubleshooting flow charts

Problem 8 – In Automatic Mode, Generator Starts When Loss of Utility Occurs, Generator

Shuts Down When Utility Returns But There Is No Retransfer To Utility Power

OR

Generator Transfers to Standby During Excercise or in Manual Mode

TEST 27 – CHECK

MANUAL TRANSFER SWITCH OPERATION

GOOD

TEST 31 – CHECK

WIRE 23

BAD REPAIR OR REPLACE MECHANISM

BAD REPAIR OR REPLACE AS NEEDED

GOOD

TEST 29 – TEST

TRANSFER

RELAY

GOOD

TEST 32 – CHECK UTILITY CONTROL CIRCUIT

BAD REPLACE

BAD REPAIR OR REPLACE AS NEEDED

Problem 9 – Blown F1 or F2 Fuse

TEST 34 – CHECK

FUSE F1 & F2

GOOD

FINISH

 

 

 

TEST 35 – CHECK

 

 

 

INSPECT/REPLACE

BAD

 

 

 

GOOD

 

 

 

 

N1 & N2 WIRING

 

 

 

PRINTED CIRCUIT BOARD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REPAIR OR REPLACE

 

 

 

 

 

 

 

WIRING

 

 

 

Page 71

Page 73
Image 73
Generac Power Systems 9 kW NG, 10 kW LP, 13 kW NG, 7 kW NG manual Troubleshooting flow charts, Problem 9 Blown F1 or F2 Fuse