Generac Power Systems 7 kW NG, 10 kW LP Harness END Remote Wireless Connection N1/N2 Connector

Models: 18 kW NG 14 kW LP 16 kW NG 20 kW LP 17 kW LP 8 kW LP 9 kW NG 7 kW NG 13 kW NG 10 kW LP

1 192
Download 192 pages 31.78 Kb
Page 102
Image 102

Section 4.1

Description and components

Part 4

DC control

18 17 16 15 14 13 12 11 10

4

3

9

8

7

6

5

4

3

2

1

2

1

J2 J1

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

J2 CONNECTOR

(PCB END)

4

3

2

1

J1 CONNECTOR

(PCB END)

J3

(STEPPER MOTOR)

3

4

10

11

12

13

14

15

16

17

18

1

2

1

2

3

4

5

6

7

8

9

J1 CONNECTOR

 

 

J2 CONNECTOR

 

 

(HARNESS END)

 

 

(HARNESS END)

 

 

1

2

REMOTE WIRELESS CONNECTION

N1/N2 CONNECTOR

N1/N2 CONNECTOR

(PCB END)

(HARNESS END)

 

Figure 6. 12/14 kW Printed Circuit Board and J1 Connector

12/14 kW J1 Connector Pin Descriptions

PIN

WIRE

CIRCUIT FUNCTION

 

 

 

J1-1

85

High temperature shutdown:

 

 

Shutdown occurs when Wire 85 is

 

 

grounded by contact closure in HTO

 

 

 

J1-2

86

Low oil pressure shutdown: Shutdown

 

 

occurs when Wire 86 is grounded by

 

 

loss of oil pressure to the LOP

 

 

 

J1-3

13

12 VDC source voltage for the circuit

 

 

board

 

 

 

J1-4

18

Ignition Shutdown: Circuit board

 

 

action grounds Wire 18 for ignition

 

 

shutdown.

 

 

 

J2-1

 

INTERNAL USE ONLY

 

 

 

J2-2

 

INTERNAL USE ONLY

 

 

 

J2-3

14

12 VDC output for engine run condi-

 

 

tion. Used for fuel solenoid and choke

 

 

solenoid operation.

 

 

 

J2-4

817

Grounded by printed circuit board to

 

 

turn on System Ready (Green) LED.

 

 

 

J2-5

23

Switched to ground for transfer relay

 

 

operation

 

 

 

J2-6

 

NOT USED

 

 

 

J2-7

 

NOT USED

 

 

 

PIN

WIRE

CIRCUIT FUNCTION

 

 

 

J2-8

15B

Provides an electrical connection for

 

 

charge current to reach the battery

 

 

from the battery charger. Provides 12

 

 

VDC to the Transfer Relay

 

 

 

J2-9

820

Positive voltage (+5 VDC) for status

 

 

LEDs.

 

 

 

J2-10

0

Common Ground

 

 

 

J2-11

56

12 VDC output to starter contactor

 

 

relay for V-Twin engines

 

 

 

J2-12

 

NOT USED

 

 

 

J2-13

818

Grounded by board to turn on the

 

 

Alarm (Red) LED.

 

 

 

J2-14

 

NOT USED

 

 

 

J2-15

90

Switched to ground for choke sole-

 

 

noid operation

 

 

 

J2-16

 

INTERNAL USE ONLY

 

 

 

J2-17

 

NOT USED

 

 

 

J2-18

 

NOT USED

 

 

 

J3

 

Control wires for Stepper Motor

 

 

 

Wired Plug-1

N1

240 VAC sensing for control board.

 

 

 

Wired Plug-2

N2

240 VAC sensing for control board.

 

 

 