Section 6.1

Major Disassembly

Part 6

Disassembly

14.Remove Blower Housing: Using a 4mm allen wrench remove one button head cap screw from top of blower housing. Using a 10mm socket remove one 10mm bolt from the top of the blower housing. See Figure 19. Using a 10mm socket remove four 10mm bolts from the right- side of the blower housing, (see Figure 20) and four 10mm bolts from the left-side of the blower housing. See Figure 21. Remove blower housing.

Figure 19.

Figure 20.

Figure 21.

Major Disassembly

Safety:

1.Set the AUTO-OFF-MANUAL switch to OFF.

2.Remove the 7.5 amp main fuse. See Figure 22.

3.Remove the N1 and N2 fuse from the transfer switch.

Figure 22. Remove 7.5 Amp Fuse

4.Turn off fuel supply to the generator and remove the flex- line from the fuel regulator.

5.Remove utility power from the generator.

6.Remove front door.

7.Remove battery from the generator.