AC generators

Part 2

Section 2.3 Troubleshooting flowcharts

General

Use the “Flow Charts” in conjunction with the detailed instructions in Section 2.4. Test numbers used in the flow charts correspond to the numbered tests in Section 2.4.

The first step in using the flow charts is to correctly identify the problem. Once that has been done, locate the problem on the following pages. For best results, perform all tests in the exact sequence shown in the flow charts.

Problem 1 - Generator Produces Zero Voltage or Residual Voltage

(12-20 kW)

TEST 1 - CHECK

MAIN CIRCUIT

BREAKER

RESET TO

“ON”

OR REPLACE

IF BAD

A

 

 

 

RE-TEST

TEST 4 - PERFORM

G

 

FIXED EXCITATION /

REPAIR

ROTOR AMP DRAW

 

 

D

OR REPLACE

B

C

FUSES

 

 

 

 

 

 

CHECK

 

 

 

VOM

 

 

 

FUSES

TEST 7 - TEST

 

GOOD

 

 

 

STATOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEST 11 -

 

 

 

 

 

 

 

 

 

GOOD

 

 

 

CHECK

 

 

 

 

 

 

 

 

 

 

ROTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RESISTANCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEST 5 - WIRE

CONTINUITY

GOOD

TEST 6 -

FIELD BOOST

BAD

GOOD

REPLACE

VOLTAGE

REGULATOR

BAD

BAD

REPAIR

OR

REPLACE

REPAIR

OR

REPLACE

THEN

RETEST

PERFORM STATOR

INSULATION

RESISTANCE TEST

-

SECTION 1.4

BAD

 

 

 

 

 

 

 

 

 

 

 

TEST 12 -

 

 

 

 

 

BAD

 

 

 

 

 

 

 

 

 

 

 

 

CHECK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BRUSHES &

 

 

 

 

 

 

 

 

 

 

 

SLIP RINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GOOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REPAIR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEST 13 -

 

OR

 

 

BAD

 

 

TEST ROTOR

 

 

 

 

REPLACE

 

 

 

 

 

 

 

ASSEMBLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GOOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PERFORM ROTOR

 

 

 

 

BAD

 

 

 

INSULATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RESISTANCE TEST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

SECTION 1.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 37

Page 39
Image 39
Generac Power Systems 18 kW NG, 10 kW LP, 13 kW NG, 7 kW NG, 9 kW NG, 8 kW LP, 17 kW LP, 20 kW LP Troubleshooting flowcharts