Dimensions & Shipping Weights for | Series 300 & 386 Transfer Switches |
UL Type 1 Enclosure (See notes below for information on Type 3R, 4 & 12 Enclosures)
Switch Rating | Phase | Neutral | Dimensions, In. (mm)3 | Approx. Shipping | ||||
amps | Poles | Code | Width | Height | Depth | Weight Lb. (kg)4 | ||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
30, 70, 100*, 104 | 2 |
| A | 17 1/2 (445) | 31 (787) | 11 5/8 (295) | 69 | (32) |
2 |
| B | 17 1/2 (445) | 31 (787) | 11 5/8 (295) | 73 | (33) | |
150, 200 |
| |||||||
3 |
| A | 17 1/2 (445) | 31 (787) | 11 5/8 (295) | 73 | (33) | |
*series 386 only |
| |||||||
3 |
| B | 17 1/2 (445) | 31 (787) | 11 5/8 (295) | 75 | (34) | |
|
| |||||||
| 2 |
| A | 18 (457) | 48 (1219) | 13 (330) | 100 (45) | |
230, 260, 400 | 2 | B7 | or C | 18 (457) | 48 (1219) | 13 (330) | 110 (50) | |
3 |
| A | 18 (457) | 48 (1219) | 13 (330) | 100 (50) | ||
|
| |||||||
| 3 | B7 | or C | 18 (457) | 48 (1219) | 13 (330) | 120 (55) | |
| 2 |
| A | 34 (864) | 72 (1829) | 20 (508) | 450 | (204) |
600, 800, 1000 | 2 |
| B | 34 (864) | 72 (1829) | 20 (508) | 475 | (217) |
3 |
| A | 34 (864) | 72 (1829) | 20 (508) | 475 | (217) | |
|
| |||||||
| 3 |
| B | 34 (864) | 72 (1829) | 20 (508) | 500 | (228) |
| 2 |
| A | 38 (965) | 87 (2210) | 24 (610) | 685 | (312) |
1200 | 2 |
| B | 38 (965) | 87 (2210) | 24 (610) | 705 | (321) |
3 |
| A | 38 (965) | 87 (2210) | 24 (610) | 705 | (321) | |
|
| |||||||
| 3 |
| B | 38 (965) | 87 (2210) | 24 (610) | 725 | (328) |
1600, 20001,6 | 3 |
| A | 38 (965) | 87 (2210) | 24 (610) | 925 | (419) |
3 |
| B | 38 (965) | 87 (2210) | 24 (610) | 975 | (441) | |
|
| |||||||
2600, 30002 | 3 |
| A | 38 (965) | 91 (2311) | 60 (1524) | 1700 (771) | |
3 |
| B | 38 (965) | 91 (2311) | 60 (1524) | 2135 (969) | ||
|
|
Series 300 & 386 External Power Connections
Sizes UL-Listed Solderless Screw-Type Terminals
Switch Rating | Ranges of | |
(amps) | (Unless Specified Copper Only) | |
|
| |
30 - 230* | One #14 to 4/0 AWG | |
260, 400 | Two 1/0 AWG to 250 MCM | |
or One #4 AWG to 600 MCM | ||
| ||
600 | Two 1/0 AWG to 600 MCM | |
800, 1000, 1200 | Four 1/0 to 600 MCM | |
1600, 2000 | Six 1/0 to 600 MCM | |
2600 | Twelve 3/0 to 600 MCM | |
3000 | Twelve 3/0 to 600 MCM |
Note: All Series 300 switches are furnished with a solid neutral plate (unless switched neutral configuration is specified) and terminal lugs. Specify A in catalog number to order a neutral plate on the series
386switches.
*200 and 230 amp rated switches for use with copper cable only.
Notes:
1.Unit is designed for top cable entry of emergency & load and bottom entry of normal. A cable pull box is also avail- able for all top or bottom cable access when required (optional accessory kit #K609027). Not required for type 3R, 4 & 12 enclosures where available.
2.Enclosures for 2600, 3000 amps are
3.For type 3R, 4 & 12 dimensions, add the following values to the type 1 dimensions:
a)30, 70, 100, 104, 150,
b)230, 260, 400A - add 1.5 in (38 mm) to the depth.
c)
d)
e)2000, 2600,
4.For type 3R, 4 & 12 weights, add the following values to the type 1 weights:
a)30, 70, 100, 104, 150,
b)230, 260, 400, 600, 800,
c)
d)
5.When temperatures below 32ºF can be experienced, special precautions should be taken, such as the inclusion of space heaters, to prevent condensation and freezing of this condensation. This is particularly important when environmental enclosures (Type 3R, 4 & 12) are ordered for installation outdoors.
6.Front connected design for 300 only,
386 dimensions are: 38"W - 91"H - 48"D.
7.Neutral Code “B” for 230 ampares only.