Series 300 ATS Optional Accessories
Accessory 11BG
A programmable engine exerciser that provides for weekly or biweekly operation, includes one form C contact for source availability of normal and one contact for availability of emergency (contact rating 2 amps @ 30 Vdc, 0.5 amp @ 125 Vac resistive). The programmable engine exerciser incorporates a 7 day or 14 day time base with a digital readout display. Includes “with or without” load control switch for exerciser period.
Accessory 14AA/14BA
Auxiliary contacts to indicate position of main contacts.Two (2) for normal and two (2) for emergency position (one set is standard).
Accessory 44A
Strip Heater with thermostat for extremely cold areas to prevent condensation and freezing of this condensation. External 120 volt power source required.
Accessory 44G
Strip Heater with thermostat, wired to load terminals:
Accessory 72A
Communications Interface Module
ASCO Pulsarfi 450 High-Performance Surge Suppressor
The ASCO Pulsarfi 450 provides unparalleled protection from power surges and transients. It is a
Fig. 10: Programmable Engine Exerciser
with Source Availability Contacts
(Accessory 11BG)
Fig. 11: Strip Heater Kit
(Accessory 44G)
Field Conversion Kits for Series 300 Transfer Switches
Kit No. | Description |
|
|
|
|
K629830 | Engine Exerciser and source availability contacts (Acc. 11BG) |
|
Strip Heater Kit (125 watt) 120 volt (Acc. 44A) |
| |
Strip Heater Kit (125 watt) |
| |
K609027 | Cable Pull Box |
|
|
| Fig. 12: Pulsar 450 |
6 FT Extension Harness* | ||
* For | Surge Suppressor | |
|
8