→TABLE 1ÐREFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID AND VAPOR TUBE DIAMETERS (IN.)
UNIT | LIQUID |
| VAPOR |
| VAPOR (LONG LINE) | |||
SIZE | Connection Diameter |
| Tube Diameter | Connection Diameter |
| Tube Diameter | Connection Diameter | Tube Diameter |
|
|
|
|
|
|
|
|
|
018 | 3/8 |
| 3/8 | 5/8 |
| 5/8 | 5/8 | 3/4 |
024 | 3/8 |
| 3/8 | 3/4 |
| 3/4 | 3/4 | 3/4 |
030, 036 | 3/8 |
| 3/8 | 3/4 |
| 3/4 | 3/4 | 7/8 |
042 | 3/8 |
| 3/8 | 7/8 |
| 7/8 | 7/8 | |
048, 060 | 3/8 |
| 3/8 | 7/8 |
| 7/8 | ||
|
|
|
|
|
|
|
|
|
NOTES:
1.Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult Residential Split System
2.Do not apply capillary tube indoor coils to these units.
PISTON BODY
PISTON
PISTON
RETAINER
X.MAKE ELECTRICAL CONNECTIONS
WARNING: To avoid personal injury or death, do not supply power to unit with compressor terminal box cover removed.
Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.
STRAINER
SWEAT/FLARE ADAPTER
→ Fig. 7ÐLiquid Service Valve
A97512
NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section
A.Route Ground and Power Wires
→ IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.
→TABLE 2ÐACCESSORY USAGE
| REQUIRED FOR | REQUIRED FOR | REQUIRED FOR | |
ACCESSORY | BURIED LINE | |||
APPLICATIONS | APPLICATIONS* | APPLICATIONS² | ||
| ||||
| (BELOW 55°F) | (OVER 50 FT) | (OVER 3 FT) | |
Crankcase Heater | Yes | Yes | Yes | |
Evaporator Freeze Thermostat | Yes | No | No | |
Accumulator | No | No | Yes | |
Compressor Start Assist | Yes | Yes | Yes | |
Capacitor and Relay | ||||
|
|
| ||
|
|
| ||
MotorMaster® Control, | Yes | No | No | |
or | ||||
|
|
| ||
|
|
| ||
Wind Baffle | See | No | No | |
Unit Risers | Recommended | No | No | |
| See |
| ||
or | No | Application | Yes | |
Hard Shutoff TXV |
| Guideline |
| |
Ball Bearing Fan Motor | Yes³ | No | No |
*For tubing line sets between 50 and 175 ft, refer to Residential Split System
³ Required for
Ð4Ð