SITRANS P measuring instruments for pressure
Transmitters for gage, absolute and differential pressure
Z series for gage pressure
2/5
Siemens FI 01 · 2009
2
Technical specifications
Dimensional drawings
SITRANSP pressure transmitters, Z series (7MF1562-...), dimensions in
mm (inch)
Schematics
SITRANSP pressure transmitters, Z series (7MF1562-...), connection dia-
gram
D) Subject to export regulations AL: N, ECCN: EAR99H.
SITRANS P pressure transmitter, Z series for gage pressure
Mode of operation
Measuring principle Thin-film strain gage
Input
Measured variable Realtive pressure
Measured range 0 to 16 bar g (0 to 232 psi g) or
0 to 25 bar g (0 to 363 psi g)
Output
Current output signal 4... 20 mA
Measuring accuracy To EN 60770-1
Error in measurement (at 25°C
(77°F), including conformity error,
hysteresis and repeatability)
0.5% of full-scale value-typical
Response time T99 < 0.1 s
Long-term drift
•Start of scale 0.3% of full-scale value/year - typ-
ical
•Measured span 0.3% of full-scale value/year - typ-
ical
Influence of ambient temperature
•Start of scale 0.3%/10K (0.3%/10 K) of full-
scale value - typical
•Measured span 0.3%/10K (0.3%/10 K) of full-
scale value - typical
Rated conditions
Medium conditions
•Process temperature -30... +120 °C (-22 ... +248 °F)
Degree of protection to EN 60529 IP65
Ambient conditions
•Ambient temperature -25... 85 °C (-13 ... +185 °F)
•Storage temperature -50 ... 100 °C (-58 ... +212 °F)
Design
Weight 0.2 kg (0.44lb)
Wetted parts materials
•Measuring cell Al 2O3 - 96%
•Process connection Brass, mat. No. 2.0402
•Gasket Viton
Process connection Male thread G½B
female thread G1/8B
Power supply
Terminal voltage on pressure trans-
mitter
•For current output 10 to 36 VDC
Certificate and approvals
Classification according to pressure
equipment directive
(DRGL97/23/EC)
For gases of fluid group 1 and
liquids of fluid 1; complies with
requirements of article 3, para-
graph 3 (sound engineering prac-
tice)
6:
G/8B
*%

0[





GLDP
1+
2-
+
Signal
R
L
U
B
I
0
I
0
Output current
U
B
Power supply
R
L
Load
Connections:
1 (+U
B
)
2 (-U
B
)
Selection and Ordering data Order No. Order code
SITRANS P pressure transmitters, Z series for pressure
2-wire system, characteristic rising
D) 7MF1562 -77700 777
Measured range Max. working pressure
0 ... 16 bar g (0 ... 232 psi g) 32 bar g (464 psi g) 3CB
0 ... 25 bar g (0 ... 363 psi g) 64 bar g (928 psi g) 3CD
Other version for measuring range 1 bar g ( 14.5 psi g), add Order code and plain text:
Measuring range: ... to ... bar g (psi g) 9AA H1Y
© Siemens AG 2008