© Siemens AG 2008

SITRANS P measuring instruments for pressure

Transmitters for gage, absolute and differential pressure, flow and level

DS III series for differential pressure and flow

Selection and Ordering data

Order No.

 

 

SITRANS P pressure transmitters

 

 

 

 

 

 

 

for differential pressure and flow

 

 

 

 

 

 

 

PN 32/160 (MWP 464/2320 psi)

 

 

 

 

 

 

 

DS III PA series (PROFIBUS PA)

7

M

F 4 4

3 4

-

 

 

DS III FF series (FOUNDATION Fieldbus)

7

M

F 4 4

3

5

-

 

 

 

 

 

 

 

 

 

77777 - 7777

Selection and Ordering data

Order No.

 

 

 

SITRANS P pressure transmitters

 

 

 

 

 

 

 

 

 

for differential pressure and flow

 

 

 

 

 

 

 

 

 

PN 32/160 (MWP 464/2320 psi)

 

 

 

 

 

 

 

 

 

DS III PA series (PROFIBUS PA)

7

M F

4

4 3 4

-

 

2

 

DS III FF series (FOUNDATION Fieldbus)

7

M F

4

4 3 5

-

 

 

 

77777

 

-

 

7777

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Measuring cell filling

Measuring cell

 

cleaning

Silicone oil

Standard

Inert liquid1)

Grease-free

Nominal measuring range

PN 32 (MWP 464 psi)

 

20 mbar2)

(8.03 inH2O)

PN 160 (MWP 2320 psi)

 

60 mbar

(24.09 inH2O)

250 mbar

(100.4 inH2O)

600 mbar

(240.9 inH2O)

1600 mbar

(642.4 inH2O)

5 bar

(2008 inH2O)

30 bar

(435 psi)

Wetted parts materials (stainless steel process flanges)

Seal diaphragm

Parts of measuring cell

Stainless steel

Stainless steel

Hastelloy

Stainless steel

Hastelloy

Hastelloy

Tantalum3)

Tantalum

Monel3)

Monel

Gold3)

Gold

Version as diaphragm seal4) 5)

Process connection

Female thread ¼-18 NPT with flange connection

Sealing screw opposite process connection

-Mounting thread 7/16-20 UNF to EN 61518

-Mounting thread M10 to DIN 19213 (only for replacement needs)

Venting on side of process flanges2)

-Mounting thread 7/16-20 UNF to EN 61518

-Mounting thread M10 to DIN 19213 (only for replacement needs)

Non-wetted parts materials

Process flange screws

Electronics housing

Stainless steel

Die-cast aluminium

Stainless steel

Stainless steel precision

 

casting

Version

Standard version

International version, English label inscriptions, documentation in 5 languages on CD

Explosion protection

Without

With ATEX, Type of protection:

-"Intrinsic safety (EEx ia)"

-"Explosion-proof (EEx d)"6)

-"Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)"7)

-"n (Zone 2)" (planned)

-"Intrinsic safety, explosion-proof enclosure

and dust explosion protection (EEx ia + EEx d + Zone 1D/2D)"7) (not for DS III FF)

With FM + CSA, Type of protection:

-"Intrinsic safety and explosion-proof (is + xp)"6)

1

3

B

C

D

E

F

G

H

A

B

C

E

H

L

Y

2

0

6 4

2

3

1

2

A

B

D

P

E

R

N C

Electrical connection / cable entry

 

 

 

 

 

• Screwed gland M20x1.5

 

B

• Screwed gland ½-14 NPT

 

C

• M12 connectors (metal)8)

 

 

 

 

 

 

F

 

Display

 

 

 

 

 

• Without indicator

 

0

 

 

 

 

 

• Without visible digital indicator (digital indicator }

 

1

 

 

hidden, setting: mA)

 

 

 

 

 

• With visible digital indication

 

6

 

 

• With customer-specific digital indication (setting

 

7

 

 

 

 

 

as specified, Order code "Y21" or required)

 

 

 

 

 

 

 

 

 

 

 

Factory-mounting of shut-off valves and valve manifolds see page 2/142.

Included in delivery of the device:

Brief instructions (Leporello)

CD-ROM with detailed documentation

Sealing plug(s) or sealing screw(s) for the process flanges(s)

1)For oxygen application, add Order code E10.

2)Not suitable for connection of remote seal. Position of the top vent valve in the process flanges (see dimensional drawing).

3)Only together with max. spans 250, 1600, 5000 and 30000 mbar (100.4, 240.9, 2008 inH2O and 435 psi).

4)When the manufacture’s certificate M (calibration certificate) has to be ordered for transmitters with diaphragm seals, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here.

5)Whe the acceptance test certificate 3.1 for transmitters with direct-con- nected diaphragm seals is ordered, this certificate must also be ordered with the corresponding seals.

6)Without cable gland, with blanking plug.

7)With enclosed cable gland EEx ia and blanking plug.

8)Cannot be used together with the following types of protection: "Explosion-proof" and "Intrinsic safety and explosion-proof".

Siemens FI 01 · 2009

2/113

Page 113
Image 113
Siemens 113, PN 32 MWP 464 psi Mbar2 03 inH2O, Wetted parts materials stainless steel process flanges