SITRANS P measuring instruments for pressure

Transmitters for gage, absolute and differential pressure, flow and level

DS III series for absolute pressure (from gage pressure series)

Technical specifications

SITRANS P, DS III series for absolute pressure (from the gage pressure series)

 

HART

 

 

 

PROFIBUS PA or FOUNDATION Fieldbus

 

 

 

 

 

 

 

 

 

 

 

Input

 

 

 

 

 

 

 

 

2

Measured variable

Absolute pressure

 

 

 

 

 

 

 

Spans (infinitely adjustable) or

Span

 

Max. perm. test

 

Nominal measuring

 

Max. perm. test

 

 

 

 

 

nominal measuring range and

 

 

pressure

 

range

 

pressure

 

max. permissible test pressure

 

 

 

 

 

 

 

 

 

 

8.3 ... 250 mbar a

 

6 bar a

 

250 mbar a

 

6 bar a

 

 

 

 

(0.12 ... 3.6 psi a)

 

(87 psi a)

 

(3.6 psi a)

 

(87 psi a)

 

43 ... 1300 mbar a

 

10 bar a

 

1300 mbar a

 

10 bar a

 

(0.62 ... 18.9 psi a)

 

(145 psi a)

 

(18.9 psi a)

 

(145 psi a)

 

160 ... 5000 mbar a

 

30 bar a

 

5 bar a

 

30 bar a

 

(2.32 ... 72.5 psi a)

 

(435 psi a)

 

(72.5 psi a)

 

(435 psi a)

 

1 ... 30 bar a

 

100 bar a

 

30 bar a

 

100 bar a

 

(14.5 ... 435 psi a)

 

(1450 psi a)

 

(435 psi a)

 

(1450 psi a)

Lower measuring limit

 

 

 

 

 

 

 

 

 

• Measuring cell with silicone oil filling

0 mbar a (0 psi a)

 

 

 

 

 

 

 

 

Upper measuring limit

100% of max. span

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

 

 

 

 

 

 

 

Output signal

4 ... 20 mA

 

 

 

Digital PROFIBUS PA or FOUNDATION Fieldbus

 

 

 

 

 

signal

 

 

 

 

• Lower limit (infinitely adjustable)

3.55 mA, factory preset to 3.84 mA

 

-

 

 

 

 

• Upper limit (infinitely adjustable)

23 mA, factory preset to 20.5 mA or optionally set

 

-

 

 

 

 

 

to 22.0 mA

 

 

 

 

 

 

 

 

Load

 

 

 

 

 

 

 

 

 

• Without HART communication

RB (UH - 10.5 V)/0.023 A in Ω,

 

 

 

 

 

 

-

 

 

 

 

 

UH : Power supply in V

 

 

 

 

 

 

 

 

• With HART communication

RB = 230 ... 500 Ω (SIMATIC PDM) or

 

-

 

 

 

 

 

RB = 230 ... 1100 Ω (HART Communicator)

 

 

 

 

 

 

Physical bus

-

 

 

 

IEC 61158-2

 

 

 

 

With polarity reversal protection

-

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Accuracy

To EN 60770-1

 

 

 

 

 

 

 

 

Reference conditions

Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling,

(All error data refer always refer to the set

room temperature 25 °C (77 °F)) r: Span ratio (r = max. span / set span)

 

 

 

 

span)

 

 

 

 

 

 

 

 

 

Error in measurement and fixed-point setting

 

 

 

 

 

 

 

 

 

(including hysteresis and repeatability)

 

 

 

 

 

 

 

 

 

• Linear characteristic

 

 

 

 

0.1%

 

 

 

 

 

 

 

 

 

 

 

 

- r 10

0.1%

 

 

 

 

 

 

 

 

- 10 < r 30

0.2%

 

 

 

 

 

 

 

 

Long-term drift (temperature change ±30 °C

(0.1 r)%/year

 

 

 

0.1%/year

 

 

 

 

(±54 °F))

 

 

 

 

 

 

 

 

 

Influence of ambient temperature

 

 

 

 

 

 

 

 

 

• at -10 ... +60 °C (14 ... 140 °F)

(0.1 r +0.2)%

 

 

 

0,3%

 

 

 

 

 

 

 

 

 

 

 

• at -40 ... -10 °C and +60 ... +85 °C

(0.1 r + 0.15)%/10 K

 

 

 

0.25%/10 K

 

 

 

 

(-40 ... +14 °F and 140 ... 185 °F)

 

 

 

 

 

 

 

 

 

Measured Value Resolution

-

 

 

 

3 10-5of nominal measuring range

Siemens FI 01 · 2009

2/89

Page 89
Image 89
Siemens technical specifications Technical specifications, Profibus PA or Foundation Fieldbus Input