SITRANS P measuring instruments for pressure

Transmitters for gage pressure for the paper industry

DS III series with PMC connection

Technical specifications

 

 

SITRANS P, DS III series for gage pressure with PMC connection for the paper industry

 

 

 

 

 

 

 

HART

 

 

 

PROFIBUS PA or FOUNDATION Fieldbus

 

 

 

 

 

 

 

 

 

 

2

 

Input

 

 

 

 

 

 

 

 

Measured variable

Gage pressure

 

 

 

 

 

 

 

 

Spans (infinitely adjustable) or

Span

 

Max. perm. test pres-

 

Nominal measuring

 

Max. perm. test pres-

 

 

 

 

 

 

 

nominal measuring range and

 

 

sure

 

range

 

sure

 

 

max. permissible test pressure

0.01 ... 1 bar g

 

6 bar g

 

1 bar g

 

6 bar g

 

 

 

 

 

 

 

 

 

(0.145 ... 14.5 psi g)

 

(87 psi g)

 

(14.5 psi g)

 

(87 psi g)

 

 

 

0.04 ... 4 bar g

 

10 bar g

 

4 bar g

 

10 bar g

 

 

 

(0.58 ... 58 psi g)

 

(145 psi g)

 

(58 psi g)

 

(145 psi g)

 

 

 

0.16 ... 16 bar g

 

32 bar g

 

16 bar g

 

32 bar g

 

 

 

(2.32 ... 232 psi g)

 

(464 psi g)

 

(232 psi g)

 

(464 psi g)

 

 

Lower measuring limit

 

 

 

 

 

 

 

 

 

• Measuring cell with silicone oil filling

100 mbar a (1.45 psi a)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Upper measuring limit

100% of max. span

 

 

 

 

 

 

Output

 

 

 

Output signal

4 ... 20 mA

 

Digital PROFIBUS PA or FOUNDATION Fieldbus

 

 

 

signal

• Lower limit (infinitely adjustable)

3.55 mA, factory preset to 3.84 mA

 

-

• Upper limit (infinitely adjustable)

23 mA, factory preset to 20.5 mA or optionally set

 

-

 

to 22.0 mA

 

 

Load

 

 

 

• Without HART communication

RB (UH - 10.5 V)/0.023 A in Ω,

 

 

-

 

UH : Power supply in V

 

 

• With HART communication

RB = 230 ... 500 Ω (SIMATIC PDM) or

 

-

 

RB = 230 ... 1100 Ω (HART Communicator)

 

 

Physical bus

-

 

IEC 61158-2

With polarity reversal protection

-

 

Yes

 

 

 

 

Accuracy

To EN 60770-1

 

 

Reference conditions

Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling,

(All error data refer always refer to the set

room temperature 25 °C (77 °F) r: Span ratio (r = max. span/set span)

span)

 

 

 

Error in measurement and fixed-point setting

 

 

 

(including hysteresis and repeatability)

 

 

 

• Linear characteristic

 

 

0,075%

 

 

- r 10

(0.0029 r + 0.071)%

 

 

- 10 < r 30

(0.0045 r + 0.071)%

 

 

- 30 < r 100

(0.005 r + 0.05)%

 

 

Long-term drift (temperature change ± 30 °C

(0.25 r)% every 5 years

 

0.25% every 5 years

(± 54 °F))

 

 

 

Influence of ambient temperature

 

 

 

• at -10 ... +60 °C (14 ... 140 °F)

(0.08 r + 0.1)%

 

0,3%

 

• at -40 ... -10 °C and +60 ... +85 °C

(0.1 r + 0.15)%/10 K

 

0.25%/10 K

(-40 ... +14 °F and 140 ... 185 °F)

 

 

 

Influence of medium temperature

 

 

 

• Temperature difference between medium

3 mbar/10 K (0.04 psi/10 K)

 

 

temperature and ambient temperature

 

 

 

Influence of mounting position

0.1 mbar g (0.00145 psi g) per 10° inclination

 

 

Measured Value Resolution

-

 

3 10-5of nominal measuring range

 

2/52

Siemens FI 01 · 2009

Page 52
Image 52
Siemens DS III series with PMC connection, Profibus PA or Foundation Fieldbus, Output signal 20 mA, Signal