SITRANS P measuring instruments for pressure

Transmitters for gage pressure for the paper industry

SITRANS P300 and DS III series with PMC connection – Technical description

SITRANS P

230 ... 500 W

Power supply

transmitter

 

 

PC or

HARTlaptop modem

RS 232

HART communication between a PC communicator and a pressure transmitter

When parameterizing with a PC, the connection is made through a HART modem.

The signals needed for communication in conformity with the HART 5.x or 6.x protocols are superimposed on the output cur- rent using the Frequency Shift Keying (FSK) method.

Adjustable parameter DS III HART and P300 HART

Parameters

Input keys

HART com-

 

 

munication

 

 

 

Start of scale

x

x

 

 

 

Full-scale value

x

x

 

 

 

Electrical damping

x

x

 

 

 

Start-of-scale value without application

x

x

of a pressure ("Blind setting")

 

 

 

 

 

Full-scale value without application of a

x

x

pressure ("Blind setting")

 

 

 

 

 

Zero adjustment

x

x

 

 

 

Current transmitter

x

x

 

 

 

Fault current

x

x

 

 

 

Disabling of keys, write protection

x

x1)

Type of dimension and actual dimension

x

x

 

 

 

Characteristic (linear)

x

x

 

 

 

Input of characteristic

 

x

 

 

 

Freely-programmable LCD

 

x

 

 

 

Diagnostics functions

 

x

1)Cancel apart from write protection

Diagnostic functions for DS III HART and P300 HART

Zero correction display

Event counter

Limit transmitter

Saturation alarm

Slave pointer

Simulation functions

Maintenance timer

Available physical units of display for DS III HART and P300

HART

Physical variable

Physical dimensions

 

 

Pressure (setting can also be

Pa, MPa, kPa, bar, mbar, torr, atm,

made in the factory)

psi, g/cm2, kg/cm2, inH O, inH

2

O

 

2

 

 

(4 °C), mmH2O, ftH2O (20 °C),

 

 

 

inHg, mmHg

 

 

Level (height data)

m, cm, mm, ft, in

 

 

Volume

m3, dm3, hl, yd3, ft3, in3, US gallon,

 

lmp, gallon, bushel, barrel, barrel

 

liquid

 

 

Mass

g, kg, t, lb, Ston, Lton, oz

 

 

Temperature

K, °C, °F, °R

 

 

Miscellaneous

%, mA

 

 

Parameterization through PROFIBUS PA interface

Fully digital communication through PROFIBUS PA, profile 3.0, is particularly user-friendly. The PROFIBUS puts the DS III PA is in connection with a process control system, e.g. SIMATIC PSC 7. Communication is possible even in a potentially explosive envi-

ronment.

 

 

2

 

 

 

For parameterization through PROFIBUS you need suitable soft-

 

ware, e.g. SIMATIC PDM (Process Device Manager).

 

Parameterization through FOUNDATION Fieldbus Interface

 

Fully digital communication through FOUNDATION Fieldbus is

 

particularly user-friendly. Through the FOUNDATION Fieldbus

 

the DS III FF is connected to a process control system. Commu-

 

nication is possible even in a potentially explosive environment.

 

For parameterization through the FOUNDATION Fieldbus you

 

need suitable software, e.g. National Instruments Configurator.

 

Adjustable parameters for DS III PA and FF and P300 PA and FF

 

 

 

 

 

Adjustable parameters

Input keys

PROFIBUS PA and

 

 

 

FOUNDATION

 

 

 

Fieldbus interface

 

 

 

 

 

Electrical damping

x

x

 

 

 

 

 

Zero adjustment (correction of

x

x

 

position)

 

 

 

 

 

 

 

Key and/or function disabling

x

x

 

 

 

 

 

Source of measured-value dis-

x

x

 

play

 

 

 

 

 

 

 

Physical dimension of display

x

x

 

 

 

 

 

Position of decimal point

x

x

 

 

 

 

 

Bus address

x

x

 

 

 

 

 

Adjustment of characteristic

x

x

 

 

 

 

 

Input of characteristic

 

x

 

 

 

 

 

Freely-programmable LCD

 

x

 

 

 

 

 

Diagnostic functions

 

x

 

Diagnostic functions for DS III PA and FF and P300 PA and FF

Event counter

Slave pointer

Maintenance timer

Simulation functions

Display of zero correction

Limit transmitter

Saturation alarm

Physical dimensions available for the display

Physical variable

Physical dimensions

Pressure (setting can also be

MPa, kPa, Pa, bar, mbar, torr, atm,

made in the factory)

psi, g/cm2, kg/cm2, mmH2O,

 

mmH2O (4 °C), inH2O, inH20

 

(4 °C), ftH2O (20 °C), mmHg, inHg

Level (height data)

m, cm, mm, ft, in, yd

Mass

g, kg, t, lb, Ston, Lton, oz

Volume

m3, dm3, hl, yd3, ft3, in3, US gallon,

 

lmp, gallon, bushel, barrel, barrel

 

liquid

Temperature

K, °C, °F, °R

Miscellaneous

%

Siemens FI 01 · 2009

2/51

Page 51
Image 51
Siemens Pressure setting can also be, Lmp, gallon, bushel, barrel, barrel, Adjustable parameters Input keys Profibus PA