SITRANS P measuring instruments for pressure

Transmitters for gage, absolute and differential pressure, flow and level

DS III series for absolute pressure (from differential pressure series)

HART communication

 

HART communication

230 ... 1100 Ω

Protocol

HART Version 5.x

Software for computer

SIMATIC PDM

 

 

PROFIBUS PA communication

 

Simultaneous communication with

4

master class 2 (max.)

 

The address can be set using

Configuration tool or local opera-

 

tion (standard setting address

 

126)

Cyclic data usage

 

Communication FOUNDATION Fieldbus

 

Function blocks

3 function blocks analog input,

 

 

1 function block PID

 

• Analog input

 

 

- Adaptation to customer-specif-

Yes, linearly rising or falling char-

2

ic process variables

acteristic

-Electrical damping T63 , adjust- 0 ... 100 s able

- Simulation function

Output/input (can be locked within

 

the device with a bridge)

- Failure mode

Can be parameterized (last good

 

value, substitute value, incorrect

 

value)

• Output byte

5 (one measuring value) or

 

10 (two measuring values)

• Input byte

0, 1, or 2 (register operating mode

 

and reset function for metering)

Internal preprocessing

 

Device profile

PROFIBUS PA Profile for Process

 

Control Devices Version 3.0,

 

Class B

- Limit monitoring

Yes, one upper and lower warning

 

limit and one alarm limit respec-

 

tively

- Square-rooted characteristic

Yes

for flow measurement

 

• PID

Standard FF function block

• Physical block

1 Resource block

Function blocks

2

• Analog input

 

- Adaptation to customer-specif-

Yes, linearly rising or falling char-

ic process variables

acteristic

-Electrical damping T63 , adjust- 0 ... 100 s able

- Simulation function

Input /Output

- Failure mode

Can be parameterized (last good

 

value, substitute value, incorrect

 

value)

- Limit monitoring

Yes, one upper and lower warning

 

limit and one alarm limit respec-

 

tively

Transducer blocks

1 transducer block Pressure with

 

calibration, 1 transducer block

 

LCD

• Pressure transducer block

 

- Can be calibrated by applying

Yes

two pressures

 

- Monitoring of sensor limits

Yes

- Simulation function: Measured

Constant value or over parameter-

pressure value, sensor temper-

izable ramp function

ature and electronics tempera-

 

ture

 

• Register (totalizer)

Can be reset, preset, optional

 

direction of counting, simulation

 

function of register output

- Failure mode

Can be parameterized (summation

 

with last good value, continuous

 

summation, summation with incor-

 

rect value)

- Limit monitoring

One upper and lower warning limit

 

and one alarm limit respectively

• Physical block

1

Transducer blocks

2

• Pressure transducer block

 

- Can be calibrated by applying

Yes

two pressures

 

- Monitoring of sensor limits

Yes

- Specification of a container

Max. 30 nodes

characteristic with

 

- Square-rooted characteristic

Yes

for flow measurement

 

- Gradual volume suppression

Parameterizable

and implementation point of

 

square-root extraction

 

- Simulation function for mea- sured pressure value and sen- sor temperature

Constant value or over parameter- izable ramp function

Siemens FI 01 · 2009

2/101