Siemens P 10 ... +85 C 14 ... +185 F, 40 ... +150 C -40 ... +302 F, 40 ... +200 C -40 ... +392 F

Models: P

1 234
Download 234 pages 4.66 Kb
Page 80
Image 80

© Siemens AG 2008

SITRANS P measuring instruments for pressure

Transmitters for gage, absolute and differential pressure, flow and level

DS III series for gage and absolute pressure, with front-flush diaphragm

 

 

SITRANS P, DS III series for gage and absolute pressure, with front-flush diaphragm

 

 

 

 

 

 

 

 

 

 

 

 

HART

 

PROFIBUS PA or FOUNDATION Fieldbus

 

 

 

 

 

 

 

 

 

Influence of ambient temperature

 

 

 

 

 

 

• at -10 ... +60 °C (14 ... 140 °F)

(0.1 r + 0.2)%

(0,2 r + 0,3)%

0,3%

0,5%

2

 

• at -40 ... -10 °C and +60 ... +85 °C

(0.1 r + 0.15)%/10 K

(0,2 r + 0,3)%/10 K

0.25%/10 K

0,5%/10 K

 

(-40 ... +14 °F and 140 ... 185 °F)

 

 

 

 

 

 

Influence of mounting position

0.1 mbar g (0.00145 psi g) per 10° inclination

 

 

 

 

Measured Value Resolution

-

 

3 10-5of nominal measuring range

 

 

 

 

 

Influence of the medium temperature (only with

 

 

 

 

 

 

front-flush diaphragm)

 

 

 

 

Temperature difference between medium tem- 3 mbar/10 K (0.04 psi/10 K) perature and ambient temperature

Rated operating conditions

 

Installation conditions

 

Ambient temperature

Observe the temperature class in areas subject to explosion hazard.

• Measuring cell with silicone oil

-40 ... +85 °C (-40 ... +185 °F)

• Measuring cell with Neobee oil (with front-flush

-10 ... +85 °C (14 ... +185 °F)

diaphragm)

 

• Measuring cell with inert liquid (not with front-

-20 ... +85 °C (-4 ... +185 °F)

flush diaphragm)

 

• Digital display

-30 ... +85 °C (-22 ... +185 °F)

• Storage temperature

-50 ... +85 °C (-58 ... +185 °F)

 

(with Neobee: -20 ... +85 °C (-4 ... +185 °F)

Climatic class

 

Condensation

Permissible

Degree of protection to EN 60529

IP65, IP68, NEMA X, enclosure cleaning, resistant to lyes, steam to 150° C (302 °F)

Electromagnetic compatibility

 

• Emitted interference and interference immunity

To EN 61326 and NAMUR NE 21

Medium conditions

 

Process temperature

 

• Measuring cell with silicone oil

-40 ... +100 °C (-40 ... +212 °F)

• Measuring cell with silicone oil (with front-flush

-40 ... +150 °C (-40 ... +302 °F)

diaphragm)

 

• Measuring cell with Neobee oil (with front-flush

-40 ... +150 °C (-40 ... +302 °F)

diaphragm)

 

• Measuring cell with silicone oil, with tempera-

-40 ... +200 °C (-40 ... +392 °F)

ture isolator (only with front-flush diaphragm)

 

• Measuring cell with inert liquid

-20 ... +100 °C (-4 ... +212 °F)

• Measuring cell with high temperature oil

-10 ... +250 °C (14 ... +482 °F)

 

 

Design

 

Weight (without options)

1.5 kg (3.3 lb)

Housing material

Poor in copper die-cast aluminium, GD-AlSi12 or stainless steel precision casting, mat. No. 1.4408

Wetted parts materials

Stainless steel, mat. No. 1.4404/316L

Measuring cell filling

Silicone oil or inert filling liquid

2/80

Siemens FI 01 · 2009

Page 80
Image 80
Siemens P technical specifications 10 ... +85 C 14 ... +185 F, 40 ... +150 C -40 ... +302 F, 40 ... +200 C -40 ... +392 F