SITRANS P measuring instruments for pressure

Transmitters for gage, absolute and differential pressure, flow and level

DS III series for gage and absolute pressure, with front-flush diaphragm

Technical specifications

SITRANS P, DS III series for gage and absolute pressure, with front-flush diaphragm

 

HART

 

 

 

PROFIBUS PA or FOUNDATION Fieldbus

 

 

 

 

 

 

 

 

 

 

 

Input gage pressure, with front-flush

 

 

 

 

 

 

 

 

2

diaphragm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Measured variable

Gage pressure, flush-mounted

 

 

 

 

 

 

Spans (infinitely adjustable) or

Span

 

Max. perm. test pres-

 

Nominal measuring

 

Max. perm. test pres-

 

 

 

 

 

nominal measuring range and

 

 

sure

 

range

 

sure

 

max. permissible test pressure

 

 

 

 

 

 

 

 

 

0.01 ... 1 bar g

 

6 bar g

 

1 bar g

 

6 bar g

 

 

 

 

 

(0.145 ... 14.5 psi g)

 

(87 psi g)

 

(14.5 psi g)

 

(87 psi g)

 

0.04 ... 4 bar g

 

10 bar g

 

4 bar g

 

10 bar g

 

(0.58 ... 58 psi g)

 

(145 psi g)

 

(58 psi g)

 

(145 psi g)

 

0.16 ... 16 bar g

 

32 bar g

 

16 bar g

 

32 bar g

 

(2.23 ... 232 psi g)

 

(464 psi g)

 

(232 psi g)

 

(464 psi g)

 

0.6 ... 63 bar g

 

100 bar g

 

63 bar g

 

100 bar g

 

(9.14 ... 914 psi g)

 

(1450 psi g)

 

(914 psi g)

 

(1450 psi g)

Lower measuring limit

-100 mbar a (-1.45 psi a)

 

 

 

 

 

 

Upper measuring limit

100% of max. span

 

 

 

100% of nominal measuring range

 

 

 

 

 

 

 

 

 

 

 

 

 

Input absolute pressure, with front-flush

 

 

 

 

 

 

 

 

 

diaphragm

 

 

 

 

 

 

 

 

 

Measured variable

Absolute pressure, flush-mounted

 

 

 

 

 

 

Spans (infinitely adjustable) or

Span

 

Max. perm. test pres-

 

Nominal measuring

 

Max. perm. test pres-

 

 

 

nominal measuring range and

 

 

sure

 

range

 

sure

max. permissible test pressure

43 ... 1300 mbar a

 

10 bar a

 

1300 mbar a

 

10 bar a

 

 

 

 

 

(0.62 ... 18.9 psi a)

 

(145 psi a)

 

(18.9 psi a)

 

(145 psi a)

 

0,16 ... 5 bar a

 

30 bar a

 

5 bar a

 

30 bar a

 

(2.32 ... 72,5 psi a)

 

(435 psi a)

 

(72,5 psi a)

 

(435 psi a)

 

1 ... 30 bar a

 

100 bar a

 

30 bar a

 

100 bar a

 

(14.5 ... 435 psi a)

 

(1450 psi a)

 

(435 psi a)

 

(1450 psi a)

 

Depending on the process connection, the span

 

Depending on the process connection, the nomi-

 

may differ from these values

 

nal measuring range may differ from these values

Lower measuring limit

0 bar a (0 psi a)

 

 

 

 

 

 

 

 

Upper measuring limit

100% of max. span

 

 

 

100% of nominal measuring range

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

 

 

 

 

 

 

 

Output signal

4 ... 20 mA

 

 

 

Digital PROFIBUS PA or FOUNDATION Fieldbus

 

 

 

 

 

signal

 

 

 

 

• Lower limit (infinitely adjustable)

3.55 mA, factory preset to 3.84 mA

 

-

 

 

 

 

• Upper limit (infinitely adjustable)

23 mA, factory preset to 20.5 mA or optionally

 

-

 

 

 

 

 

set to 22.0 mA

 

 

 

 

 

 

 

 

Load

 

 

 

 

 

 

 

 

 

• Without HART communication

RB (UH - 10.5 V)/0.023 A in Ω,

 

 

 

 

 

 

-

 

 

 

 

 

UH : Power supply in V

 

 

 

 

 

 

 

 

• With HART communication

RB = 230 ... 500 Ω (SIMATIC PDM) or

 

-

 

 

 

 

 

RB = 230 ... 1100 Ω (HART Communicator)

 

 

 

 

 

 

Physical bus

-

 

 

 

IEC 61158-2

 

 

 

 

With polarity reversal protection

-

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Accuracy

To EN 60770-1

 

 

 

 

 

 

 

 

Reference conditions

Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil fill-

(All error data refer always refer to the set span)

ing, room temperature 25 °C (77 °F)) r: Span ratio (r = max. span/set span)

Error in measurement and fixed-point setting

 

 

 

 

 

 

 

 

 

(including hysteresis and repeatability)

 

 

 

 

 

 

 

 

 

 

Gage pressure,

 

Absolute pressure,

 

Gage pressure,

 

Absolute pressure,

 

 

 

 

 

front-flushed

 

front-flushed

 

front-flushed

 

front-flushed

• Linear characteristic

 

 

 

 

0,075%

 

0,2%

- r 10

(0.0029 r + 0.071)%

 

0,2%

 

 

 

 

 

 

- 10 < r 30

(0.0045 r + 0.071)%

 

0,4%

 

 

 

 

 

 

- 30 < r 100

(0.005 r + 0.05)%

 

-

 

 

 

 

 

 

Long-term drift (temperature change ±30 °C

(0.25 r)% every 5

 

 

 

0.25% every 5 years

 

 

 

 

(±54 °F))

years

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Siemens FI 01 · 2009