Transmitters for gage, absolute and differential pressure, flow and level

DS III series for gage pressure

Selection and Ordering data

Order No.

 

SITRANS P pressure transmitters for gage

 

 

pressure

 

 

 

DS III PA (PROFIBUS PA) series

7 M F 4 0 3 4 -

DS III FF series (FOUNDATION Fieldbus)

7 M F 4 0 3 5 -

 

 

77777 -

7777

Measuring cell filling

Measuring cell

 

 

 

cleaning

 

 

Silicone oil

Standard

1

 

Inert liquid1)

Grease-free

3

 

Nominal measuring range

 

 

1 bar g

(14.5 psi g)

B

 

4 bar g

(58 psi g)

C

 

16 bar g

(232 psi g)

D

 

63 bar g

(914 psi g)

E

 

160 bar g

(2320 psi g)

F

 

400 bar g

(5802 psi g)

G

 

700 bar g

(10153 psi g)

J

 

Wetted parts materials

 

 

 

Seal diaphragm

Process connection

 

 

Stainless steel

Stainless steel

A

 

Hastelloy

Stainless steel

B

 

Hastelloy

Hastelloy

C

 

Version as diaphragm seal2) 3)

Y

 

Process connection

 

 

 

• Connection shank G½A to EN 837-1

0

 

• Female thread ½-14 NPT

1

 

• Oval flange made of stainless steel

 

 

- Mounting thread 7/16-20 UNF to EN 61518

2

 

- Mounting thread M10 to DIN 19213

3

 

- Mounting thread M12 nach DIN 19213

4

 

• Male thread M20 x 1,5

 

5

 

• Male thread ½-14 NPT

 

6

 

Non-wetted parts materials

 

 

• Housing made of die-cast aluminium

0

 

• Housing stainless steel precision casting

3

 

Version

 

 

 

• Standard version

 

 

1

• International version, English label inscriptions,

 

2

documentation in 5 languages on CD

 

 

Explosion protection

 

 

 

• Without

 

 

A

• With ATEX, Type of protection:

 

 

- "Intrinsic safety (EEx ia)"

 

B

- "Explosion-proof (EEx d)"4)

 

D

- "Intrinsic safety and explosion-proof enclosure

 

P

(EEx ia + EEx d)"5)

 

 

 

- "Ex nA/nL (zone 2)"

 

 

E

- "Intrinsic safety, explosion-proof enclosure and

 

R

dust explosion protection (EEx ia + EEx d +

 

 

Zone 1D/2D)"6) (not for DS III FF)

 

 

• With FM + CSA, Type of protection:

 

 

- "Intrinsic safety and explosion-proof

 

N C

(is + xp)"5)

 

 

 

Electrical connection / cable entry

 

 

• Screwed gland M20x1.5

 

 

B

• Screwed gland ½-14 NPT

 

 

 

 

C

• Plug M12 (metal)6)

 

 

F

Selection and Ordering data

Order No.

 

SITRANS P pressure transmitters for gage

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

 

 

 

 

 

 

 

DS III PA (PROFIBUS PA) series

 

 

 

 

 

 

 

 

 

 

7

M F

4

0 3 4

 

-

 

 

DS III FF series (FOUNDATION Fieldbus)

7

M F

4

0 3 5

-

 

 

2

 

 

77777

 

-

 

7777

 

 

 

Display

 

 

 

 

 

 

 

 

 

 

 

 

• Without indicator

 

 

 

 

 

 

 

 

0

 

 

 

• Without visible digital indicator (digital indicator }

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

hidden, setting: mA)

 

 

 

 

 

 

 

 

 

 

 

 

• With visible digital indicator

 

 

 

 

 

 

 

 

6

 

 

 

• With customer-specific digital indicator (setting

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

as specified, Order code "Y21" or required)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory-mounting of shut-off valves and valve manifolds see page 2/142.

The device is delivered together with brief instructions (Leporello) and a CD-ROM containing detailed documentation.

1)For oxygen application, add Order code E10.

2)When the manufacture’s certificate M (calibration certificate) has to be ordered for transmitters with diaphragm seals, it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here.

3)Whe the acceptance test certificate 3.1 for transmitters with direct-con- nected diaphragm seals is ordered, this certificate must also be ordered with the corresponding seals.

4)Without cable gland, with blanking plug.

5)With enclosed cable gland EEx ia and blanking plug.

6)Cannot be used together with the following types of protection: "Explosion-proof" and "Intrinsic safety and explosion-proof"