SITRANS P measuring instruments for pressure

Transmitters for gage, absolute and differential pressure, flow and level

DS III series for gage and absolute pressure, with front-flush diaphragm

 

 

HART communication

 

 

 

HART communication

230 ... 1100 Ω

 

 

Protocol

HART Version 5.x

 

 

Software for computer

SIMATIC PDM

2

 

 

 

 

PROFIBUS PA communication

 

 

 

Simultaneous communication with

4

 

 

master class 2 (max.)

 

 

 

The address can be set using

Configuration tool or local opera-

 

 

 

 

tion (standard setting address

 

 

 

126)

 

 

Cyclic data usage

 

 

 

• Output byte

5 (one measuring value) or

 

 

 

10 (two measuring values)

 

 

• Input byte

0, 1, or 2 (register operating mode

 

 

 

and reset function for metering)

 

 

Internal preprocessing

 

 

 

Device profile

PROFIBUS PA Profile for Process

 

 

 

Control Devices Version 3.0,

 

 

 

Class B

 

 

Function blocks

2

 

 

• Analog input

 

 

 

- Adaptation to customer-specif-

Yes, linearly rising or falling char-

 

 

ic process variables

acteristic

 

 

- Electrical damping T63 , adjust-

0 ... 100 s

 

 

able

 

 

 

- Simulation function

Input /Output

 

 

- Failure mode

Can be parameterized (last good

 

 

 

value, substitute value, incorrect

 

 

 

value)

 

 

- Limit monitoring

Yes, one upper and lower warning

 

 

 

limit and one alarm limit respec-

 

 

 

tively

 

 

• Register (totalizer)

Can be reset, preset, optional

 

 

 

direction of counting, simulation

 

 

 

function of register output

 

 

- Failure mode

Can be parameterized (summation

 

 

 

with last good value, continuous

 

 

 

summation, summation with incor-

 

 

 

rect value)

 

 

- Limit monitoring

One upper and lower warning limit

 

 

 

and one alarm limit respectively

 

 

• Physical block

1

 

 

Transducer blocks

2

 

 

• Pressure transducer block

 

 

 

- Can be calibrated by applying

Yes

 

 

two pressures

 

 

 

- Monitoring of sensor limits

Yes

 

 

- Specification of a container

Max. 30 nodes

 

 

characteristic with

 

 

 

- Square-rooted characteristic

Yes

 

 

for flow measurement

 

 

 

- Gradual volume suppression

Parameterizable

 

 

and implementation point of

 

 

 

square-root extraction

 

 

 

- Simulation function for mea-

Constant value or over parameter-

 

 

sured pressure value and sen-

izable ramp function

 

 

sor temperature

 

Communication FOUNDATION Fieldbus

Function blocks

3 function blocks analog input,

 

1 function block PID

• Analog input

 

- Adaptation to customer-specif-

Yes, linearly rising or falling char-

ic process variables

acteristic

-Electrical damping T63 , adjust- 0 ... 100 s able

- Simulation function

Output/input (can be locked within

 

the device with a bridge)

- Failure mode

Can be parameterized (last good

 

value, substitute value, incorrect

 

value)

- Limit monitoring

Yes, one upper and lower warning

 

limit and one alarm limit respec-

 

tively

- Square-rooted characteristic

Yes

for flow measurement

 

• PID

Standard FF function block

• Physical block

1 Resource block

Transducer blocks

1 transducer block Pressure with

 

calibration, 1 transducer block

 

LCD

• Pressure transducer block

 

- Can be calibrated by applying

Yes

two pressures

 

- Monitoring of sensor limits

Yes

- Simulation function: Measured

Constant value or over parameter-

pressure value, sensor temper-

izable ramp function

ature and electronics tempera-

 

ture

 

2/82

Siemens FI 01 · 2009