SITRANS P measuring instruments for pressure

Transmitters for gage pressure for the paper industry

SITRANS P300 with PMC connection

SITRANS P300 for gage pressure with PMC connection for the paper industry

 

HART communication

 

 

HART communication

230 ... 1100 Ω

2

Protocol

HART Version 5.x

Software for computer

SIMATIC PDM

PROFIBUS PA communication

 

Simultaneous communication with

4

master class 2 (max.)

 

The address can be set using

configuration tool

 

Local operation

 

(standard setting Address 126)

Cyclic data usage

 

• Output byte

One measuring value: 5 bytes

 

Two measuring values: 10 bytes

• Input byte

Register operating mode: 1 bytes

 

Reset function due to metering.

 

1 bytes

Device profile

PROFIBUS PA Profile for Process

 

Control Devices Version 3.0,

 

Class B

Function blocks

2

• Analog input

 

- Adaptation to customer-specific

Linearly rising or falling character-

process variables

istic

- Electrical damping T63

0 ... 100 s adjustable

- Simulation function

Input /Output

- Limit monitoring

One upper and lower warning limit

 

and one alarm limit respectively

• Register (totalizer)

Can be reset and preset

 

Optional direction of counting

 

Simulation function of the register

 

output

- Limit monitoring

One upper and lower warning limit

 

and one alarm limit respectively

• Physical block

1

Transducer blocks

2

• Pressure transducer block

 

- Monitoring of sensor limits

Yes

- Specification of a container

Max. 31 nodes

characteristic with

 

- Characteristic

Linear

- Simulation function

Available

• Transducer block "Electronic tem-

 

perature"

 

- Simulation function

Available

Communication FOUNDATION Fieldbus

Function blocks

3 function blocks analog input,

 

1 function block PID

• Analog input

 

- Adaptation to customer-specif-

Yes, linearly rising or falling char-

ic process variables

acteristic

-Electrical damping T63 , adjust- 0 ... 100 s able

- Simulation function

Output/input (can be locked within

 

the device with a bridge)

- Failure mode

Can be parameterized (last good

 

value, substitute value, incorrect

 

value)

- Limit monitoring

Yes, one upper and lower warning

 

limit and one alarm limit respec-

 

tively

- Square-rooted characteristic

Yes

for flow measurement

 

• PID

Standard FF function block

• Physical block

1 Resource block

Transducer blocks

1 transducer block Pressure with

 

calibration, 1 transducer block

 

LCD

• Pressure transducer block

 

- Can be calibrated by applying

Yes

two pressures

 

- Monitoring of sensor limits

Yes

- Simulation function: Measured

Constant value or over parameter-

pressure value, sensor temper-

izable ramp function

ature and electronics tempera-

 

ture

 

2/60