Emerson SL-19534 Dual Unit Control Board, Jumper settings for servicing InteleCool2 unit

Page 6
Figure 1 Dual Unit Control Board

Control Startup

Figure 1 Dual Unit Control Board

1

2

P5

P5

P4

Reverse

Normal

to LED

 

Panel

3

4

 

 

R

 

DRAWING IS

1/2

Unit

Y

2

NOT TO SCALE

 

 

 

W

 

 

R

 

 

1/2

Unit

 

Y

1

 

W

 

 

 

TB1

1

2

Slow

P3

Fast

 

3

4

P1

1

2

3P1 to

4Thermostat

5

6

7

8/4Day

4/2Day

2/1Day

Lead1

Lead2

S e

P2 r

v i c e

! WARNING

InteleCool and InteleCool2 units contain potentially lethal voltage. Shut off power before performing any service work.

During service, the P2 jumper should be placed on the pins that identify the unit NOT being serviced. Refer to Table 2 for required jumper pin connections. The P2 setting will override the lead unit setting until the jumper is returned to the proper number-of-days location.

Table 2

Jumper settings for servicing InteleCool2 unit

 

 

 

To service desired unit

Jumper Settings P2

Jumper Setting P4

 

 

 

 

 

Unit 1

Lead 2

Pins 3 & 4 (normal)

 

 

 

 

 

Unit 2

Lead 1

Pins 3 & 4 (normal)

 

 

 

 

4

Image 6
Contents Liebert Dual Unit Control for InteleCool and InteleCool2 Precision CoolingFor Business-Critical Continuity 3.0 DISPOSAL OF DUAL UNIT CONTROL 1.0 INSTALLATION2.0 CONTROL STARTUP TABLE OF CONTENTS1.1 Connecting the Dual Unit Controller to an Electronic Thermostat 1.0 INSTALLATION1.1.1 Connecting the Dual Unit Controller to an InteleCool2 1.1.2 Connecting the Dual Unit Controller to the InteleCool 2.3 Lead Unit Schedule & Selection 2.1 Start the Dual Unit Control2.2 Check for Operation 2.0 CONTROL STARTUPJumper Settings P2 Jumper settings for servicing InteleCool2 unitTo service desired unit Jumper Setting P43.0 DISPOSAL OF DUAL UNIT CONTROL Disposal of Dual Unit ControlNe t Ensuring The High Availability0f Mission-Critical Data And Applications ti n