Emerson 00825-0100-4075 manual Physical Installation, Direct Mount

Page 5

Quick Installation Guide

00825-0100-4075, Rev BA February 2010

Smart Wireless THUM Adapter

Figure 3. THUM Adapter Only, Powered by a 24 V Power Supply with 1200 Ohm resistor to limit current to 20 mA

THUM Adapter

Green

Ground

Red

+

Black

20 mA

Current

 

White

- Source

Yellow

1200

Ohm

 

Resistor

 

HART

 

Modem

STEP 1: PHYSICAL INSTALLATION

 

The THUM Adapter can be installed in one of two configurations:

Direct Mount: The THUM Adapter is connected directly to the conduit entry of the wired device.

Figure 4. Direct Mount

Direct Mount

1.Install the HART device according to standard installation practices and the manufacturer’s instructions, being sure to use an approved thread sealant on all connections.

2.Attach the THUM Adapter to the wired device as shown in Figure 4.

3.Connect the THUM Adapter to the HART wired device using the wiring diagrams below. See Figures 21, 8, 10, and 12 on the following pages.

4.Close the housing cover on the HART wired device, so that metal touches metal, but do not over tighten to prevent damaging the unit.

NOTE

Two splice connectors are included with the THUM Adapter. The first is a two connection splice. The second is a three connection splice for use with a resistor, if there is not enough resistance in the loop. Both of these splice connectors can accept 14 to 22 gauge wire. See wired device reference manual for information on the required loop resistance.

5

Image 5
Contents Quick Installation Guide Smart Wireless Thum AdapterImportant Notice Power Up Sequence Wireless ConsiderationsThum Adapter Position Conduit EntryLoad Resistor Bench TOP ConfigurationPower Supply Direct Mount Physical InstallationRemote Mount Remote MountWiring Diagrams Remote Mount Wiring Diagram for 2-Wire Device Remote Mount Wiring Diagram for 2-Wire Device with Resistor Remote Mount Wiring Diagram for 4-Wire Passive Device Green Black Remote Mount Wiring Diagram for 4-Wire Active Device Power+ GroundResistor Power + Ohm Resistor Junction Box Field Communicator Device Network ConfigurationAMS AMS Loop Current TestAMS Configure screen AMS Wireless Configurator Smart Wireless GatewayVerify Operation Field CommunicatorReference Information TroubleshootingProduct Certifications European Directive InformationCSA Canadian Standards Association North American CertificationsEuropean Certifications Hazardous Locations CertificatesIECEx Certifications EC Declaration of Conformity EC Declaration of Conformity Atex Notified Bodies for EC Type Examination Certificate Smart Wireless Thum Adapter Smart Wireless Thum Adapter