Emerson 00825-0100-4075 manual Loop Current Test, Ams

Page 17

Quick Installation Guide

00825-0100-4075, Rev BA February 2010

Smart Wireless THUM Adapter

Loop Current Test

To verify that the THUM Adapter will work under all conditions, a loop current test should be performed. This test will exercise the loop under the highest possible voltage drop conditions.

1.Place loop in manual control.

2.Drive loop to high alarm level. For details see wired device instruction manual.

When the THUM Adapter is connected to a valve, this will need to be done at the current source and not from the valve.

When the THUM Adapter is connected to a transmitter, this will need to be performed at the transmitter.

3.Place the THUM Adapter into fixed voltage drop mode.

AMS

Right click on the THUM Adapter and select Configure. When the menu opens, select Manual Setup from the window on the left and select the Wired Device tab on the top. Make sure that the Time drop down menu at the bottom of the page has Current selected. Under the Voltage Drop drop down menu in the Smart Power Options box, select Fixed Voltage Drop. Hit the Apply button to make any changes. See Figure 23 on page 18.

Field Communicator

When communicating to the THUM Adapter select: Configure - Manual setup - Wired Device - Voltage Drop Mode. In the method choose Fixed Voltage Drop.

 

 

 

Function

Key Sequence

Menu Items

Voltage Drop

2,2,2,2

Voltage Drop

4.Verify that the current on the loop reaches the high alarm levels.

5.Place the THUM Adapter into variable voltage drop mode.

AMS

Right click on the THUM Adapter and select Configure. When the menu opens, select Manual Setup from the window on the left and select the Wired Device tab on the top. Make sure that the Time drop down menu at the bottom of the page has Current selected. Under the Voltage Drop drop down menu in the Smart Power Options box, select Variable Voltage Drop. Hit the Apply button to make any changes. See Figure 23.

Field Communicator

When communicating to the THUM Adapter select: Configure - Manual setup - Wired Device - Voltage Drop Mode. In the method choose Variable Voltage Drop.

 

 

 

Function

Key Sequence

Menu Items

Voltage Drop

2,2,2,2

Voltage Drop

17

Image 17
Contents Quick Installation Guide Smart Wireless Thum AdapterImportant Notice Power Up Sequence Wireless ConsiderationsThum Adapter Position Conduit EntryLoad Resistor Bench TOP ConfigurationPower Supply Direct Mount Physical InstallationRemote Mount Remote MountWiring Diagrams Remote Mount Wiring Diagram for 2-Wire Device Remote Mount Wiring Diagram for 2-Wire Device with Resistor Remote Mount Wiring Diagram for 4-Wire Passive Device Green Black Remote Mount Wiring Diagram for 4-Wire Active Device Power+ GroundResistor Power + Ohm Resistor Junction Box Field Communicator Device Network ConfigurationAMS AMS Loop Current TestAMS Configure screen AMS Wireless Configurator Smart Wireless GatewayVerify Operation Field CommunicatorReference Information TroubleshootingProduct Certifications European Directive InformationCSA Canadian Standards Association North American CertificationsEuropean Certifications Hazardous Locations CertificatesIECEx Certifications EC Declaration of Conformity EC Declaration of Conformity Atex Notified Bodies for EC Type Examination Certificate Smart Wireless Thum Adapter Smart Wireless Thum Adapter