Quick Installation Guide
Smart Wireless THUM Adapter
IECEx Certifications
I7 IECEx Intrinsic Safety
Certificate No.: IECEx BAS 09.0050X
Ex ia IIC T4
IP66
Table 3. Input Parameters
Loop Power
Ui = 30V
Ii = 200 mA
Pi = 1.0 W
Ci = 0
Li = 0
Special conditions for safe use (X)
The surface resistivity of the antenna is greater than one gigaohm. To avoid electrostatic charge
The enclosure is made of aluminium alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0.
N7 IECEx Type n
Certificate No.: IECEx BAS 09.0058
Ex nA IIC T4
Ui = 45 Vdc MAX
IP66
23