Emerson 00825-0100-4075 manual North American Certifications, CSA Canadian Standards Association

Page 22

Quick Installation Guide

Smart Wireless THUM Adapter

00825-0100-4075, Rev BA February 2010

Hazardous Locations Certificates

North American Certifications

Factory Mutual (FM) Approvals

I5 FM Intrinsically Safe and Non-incendive

Intrinsically Safe for Class I/II/III, Division 1, Groups A, B, C, D, E, F, and G. Zone Marking: Class I, Zone 0, AEx ia llC

Temperature Codes T4 (-50 °C Tamb 70 °C) Non-incendive for Class I, Division 2, Groups A, B, C, and D.

Intrinsically safe and non-incendive when installed according to Rosemount Drawing 00775-0010.

Enclosure Type 4X/IP66

CSA - Canadian Standards Association

I6 CSA Intrinsically Safe

Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D. T3C (-50 °C Tamb 70 °C)

Intrinsically safe when installed according to Rosemount Drawing 00775-0012. Suitable for Class I, Division 2, Groups A, B, C, and D.

Enclosure Type 4X/IP66

European Certifications

I1 ATEX Intrinsic Safety

Certificate No.: Baseefa09ATEX0125X II 1G Ex ia IIC T4 (-50 °C Tamb 70 °C)

IP66

1180

Table 2. Input Parameters

Loop Power

Ui = 30V

Ii = 200 mA

Pi = 1.0 W

Ci = 0

Li = 0

Special conditions for safe use (X)

The surface resistivity of the antenna is greater than one gigaohm. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.

The enclosure is made of aluminium alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0.

N1 ATEX Type n

 

Certificate No.: Baseefa09ATEX0131

II 3 G

Ex nA IIC T4 (-50 °C Tamb 70 °C)

 

Ui = 45 Vdc MAX

 

IP66

 

1180

 

22

Image 22
Contents Smart Wireless Thum Adapter Quick Installation GuideImportant Notice Thum Adapter Position Wireless ConsiderationsPower Up Sequence Conduit EntryPower Supply Bench TOP ConfigurationLoad Resistor Physical Installation Direct MountRemote Mount Remote MountWiring Diagrams Remote Mount Wiring Diagram for 2-Wire Device Remote Mount Wiring Diagram for 2-Wire Device with Resistor Remote Mount Wiring Diagram for 4-Wire Passive Device Green Black Remote Mount Wiring Diagram for 4-Wire Active Device Power+ GroundResistor Power + Ohm Resistor Junction Box AMS Device Network ConfigurationField Communicator Loop Current Test AMSAMS Configure screen Verify Operation Smart Wireless GatewayAMS Wireless Configurator Field CommunicatorTroubleshooting Reference InformationEuropean Directive Information Product CertificationsEuropean Certifications North American CertificationsCSA Canadian Standards Association Hazardous Locations CertificatesIECEx Certifications EC Declaration of Conformity EC Declaration of Conformity Atex Notified Bodies for EC Type Examination Certificate Smart Wireless Thum Adapter Smart Wireless Thum Adapter