Cisco Systems 5000 Series manual Requirements Specific to Perforated Cabinets, Rittal Corporation

Page 84

Appendix A Cabinet and Rack Installation

Cabinet and Rack Requirements

Se n d d o c u m e n t a t i o n c o m m e n t s t o n ex u s 5 k d o c s @ c i s c o . c o m

The minimum vertical rack space per 5010 chassis must be one RU (rack unit), equal to 1.75 inches (4.4 cm).

The width between the rack-mounting rails must be at least 17.75 inches (45.1 cm) if the rear of the switch is not attached to the rack. For four-post EIA racks, this is the distance between the two front rails.

For four-post EIA cabinets (perforated or solid-walled):

The minimum spacing for the bend radius for fiber-optic cables should have the front-mounting rails of the cabinet offset from the front door by a minimum of 3 inches (7.6 cm), and a minimum of 5 inches (12.7 cm) if cable management brackets are installed on the front of the chassis.

The distance between the outside face of the front mounting rail and the outside face of the back mounting rail should be 23.5 to 34.0 inches (59.7 to 86.4 cm) to allow for rear-bracket installation.

A minimum of 2.5 inches (6.4 cm) of clear space should exist between the side edge of the chassis and the side wall of the cabinet. No sizeable flow obstructions should be immediately in the way of chassis air intake or exhaust vents.

Note Optional jumper power cords are available for use in a cabinet. See the “Jumper Power Cord” section on page C-10.

Requirements Specific to Perforated Cabinets

A perforated cabinet is defined here as a cabinet with perforated front and rear doors and solid side walls. In addition to the requirements listed in the “General Requirements for Cabinets and Racks” section on page A-1, perforated cabinets must meet the following requirements:

The front and rear doors must have at least a 60 percent open area perforation pattern, with at least 15 square inches of open area per rack unit of door height.

The roof should be perforated with at least a 20 percent open area.

The cabinet floor should be open or perforated to enhance cooling.

A perforated cabinet that conforms to these requirements is available from Rittal Corporation:

Rittal Corporation

One Rittal Place

Springfield, OH 45504

Contact: (800) 477–4220

Cabinet P/N: Rittal 9969427

Cabinet description: PS-DK/OEM Cabinet Assembly, (78.7 in.) 1998 mm X 23.6 in. (600 mm) X 39.4 in. (1000 mm) (H x W x D) (42 RU)

Cisco Nexus 5000 Series Hardware Installation Guide

 

A-2

OL-15902-01

 

 

 

Image 84
Contents Cisco Nexus 5000 Series Hardware Installation Guide Americas HeadquartersCisco Nexus 5000 Series Hardware Installation Guide Iii SFP+ Copper Cables Cable Management Guidelines Switch Specifications Chassis and Module Information D-4 Overview E-1 Audience OrganizationChapter Title Description Conventions Chapter Title DescriptionWarnung Wichtige Sicherheitshinweise Avvertenza Importanti Istruzioni Sulla SicurezzaAviso Instruções Importantes DE Segurança Guarde Estas InstruçõesGEM Disse Anvisninger Xii Xiii Related Documentation Nexus 5020 Switch FeaturesTwo power supplies Five fan modules ChassisCisco Nexus 5020 Switch Rear View Internal cross connect ports Network management ports Expansion Modules Fibre Channel Plus Ethernet Expansion ModuleStatus Description Ethernet Expansion Module Six 10-Gigabit Ethernet ports Module LEDN5K-M1008 LEDPorts Power Supply 13 Power Supply for the Cisco Nexus 5020 SwitchPower Supply Condition Power LED Status Fail LED Status Fan Module15 Cisco Nexus 5020 Fan Module LED Descriptions Location Function Color Status DescriptionLED Supported SFP Transceivers SFP+ TransceiversSFP+ Copper Cables ModelNexus 5010 Switch SFP Fiber Channel TransceiversModel Description 17shows the front of the Cisco Nexus 5010 switch 18shows a close-up view of the front of the switch Product Overview Nexus 5010 Switch 20 Cisco Nexus 5010 Switch Rear View Close-up N5K-M1404 22 N5K-M1404 Gatos Expansion ModuleN5K-M1600 23 Front of the N5K-M1404 GEM25 N5K-M1008 GEM 192241 192242 30 Power Supply for the Cisco Nexus 5010 Switch 31 Blank Power Supply Filler Panel Fan module LED Port Level LED’s Link State LED StateDS-SFP-FC4G-SW Product Overview Nexus 5010 Switch Installing the Cisco Nexus 5000 Switch Preparing for Installation Installation OptionsChassis Weight Airflow ConsiderationsInstallation Guidelines Unpacking and Inspecting the Switch Required EquipmentQuantity Part Description Slider railsFront rack-mount bracket Slider rail Rack-mount guides Installing the Slider Rails Installing the Cisco Nexus 5010 Chassis in a Cabinet or Rack 273161 Grounding the System Proper Grounding PracticesEnvironment Level Grounding Recommendations Preventing Electrostatic Discharge Damage Attaching the ESD Wrist Strap to the System Ground Lug Screw Establishing the System Ground Required Tools and EquipmentGrounding the Chassis Location of System Ground on a Cisco Nexus 5000 Switch Starting the Switch Removing and Installing Components Removing and Installing Expansion Modules Installing an Expansion ModuleRemoving an Expansion Module Positioning the Module in the Cisco Nexus 5020 ChassisRemoving and Installing Power Supplies Removing a Power SupplyInstalling a Power Supply 11 Removing the Power Supply for the Cisco Nexus 5020 switchRemoving and Installing the Fan Module 13 Fan Module for the Cisco Nexus 5020 switch Removing a Fan ModuleRemoving the Cisco Nexus 5000 Switch Installing a Fan ModuleRepacking the Cisco Nexus 5000 Switch for Return Shipment Connecting the Cisco Nexus 5000 Switch Connecting to the Console Port Preparing for Network ConnectionsConnecting to the Ethernet Connector Port Connecting to an Ethernet Port Removing and Installing SFP+ TransceiversInstalling an SFP+ Transceiver Removing an SFP+ TransceiverAlternate Removal Method for Bale Clasp SFP+ Transceivers Removing and Installing Cables into SFP+ Transceivers Installing a Cable into an SFP+ TransceiverRemoving a Cable from an SFP+ Transceiver Connecting to a Fibre Channel Port Removing and Installing SFP TransceiversInstalling an SFP Transceiver Maintaining SFP+ Transceivers and CablesRemoving an SFP Transceiver Removing and Installing Cables into SFP Transceivers Installing a Cable into an SFP TransceiverConnecting the LC-Type Cable to a Fibre Channel Port Removing a Cable from an SFP TransceiverMaintaining SFP Transceivers and Fiber-Optic Cables Cisco Nexus 5000 Series Hardware Installation Guide Cabinet and Rack Requirements General Requirements for Cabinets and RacksRequirements Specific to Perforated Cabinets Rittal CorporationCable Management Guidelines Requirements Specific to Solid-Walled CabinetsRequirements Specific to Standard Open Racks Cisco Nexus 5000 Series Hardware Installation Guide Switch Specifications Description SpecificationExpansion Module Specifications Power SpecificationsSpecifications for the Cisco Nexus 5020 Power Supply Specifications for the Cisco Nexus 5010 Power Supply Power Supply LED IndicatorsCondition Power LED Status Green Fail LED Status Amber Transceiver Specifications Parameter Symbol Min Max UnitDescription Short Range Description Short Wavelength MMFCisco Nexus 5000 Series Hardware Installation Guide Accessory Kit for the Cisco Nexus 5020 Switch Accessory Kit for the Cisco Nexus 5010 SwitchCable RJ-45 Connector Pinouts Signal Name P1, P1-45 Pins P2, DB-9 PinsConsole Cable Pin Signal Console PortConsole Port Pinouts Supported Power Cords and Plugs Power CordsLength Description Feet Meters IllustrationAC Power Cord Illustrations CAB-9K10A-UKCAB-9K10A-AU Plug VSCC15 BKR CAB-9K12A-NA Jumper Power Cord Figure C-16 CAB-C13-C14-JMPR, Jumper Power CordSite Planning and Maintenance Records Site Preparation ChecklistTask No Planning Activity Verified By Time Date Contact and Site Information Chassis and Module Information Slot Module Type Module Serial Number SupervisorSwitch Hardware Best Practices OverviewSnmp Traps Installation Best Practices Switch Operation Best PracticesInitialization Best Practices Numerics IN-2 IN-3 IN-4

5000 Series specifications

Cisco Systems 5000 Series is a comprehensive line of network switches designed to provide robust performance, high scalability, and exceptional flexibility for various enterprise applications. This switch series is ideally suited for environments such as data centers and large-scale enterprise networks, addressing the demands of modern networking by delivering high-speed connectivity along with advanced features.

One of the standout features of the Cisco 5000 Series is its support for hybrid environments, allowing deployment in both on-premises data centers and cloud-based architectures. With enhanced support for modern networking paradigms, such as Software-Defined Networking (SDN), the switches facilitate seamless integration into existing infrastructure while optimizing resource utilization. Cisco's Application Centric Infrastructure (ACI) technology enhances application performance and availability across diverse workloads and applications.

The 5000 Series delivers superior performance with fixed and modular configurations tailored to different operational demands. This flexibility allows businesses to select from various models that best fit their specific needs, whether they require high-density 10, 25, 40, or 100 Gigabit Ethernet connectivity. The series supports high throughput and low latency, making it ideal for data-intensive applications such as virtualization and real-time data processing.

High availability is another critical aspect of the Cisco 5000 Series, which incorporates redundant hardware components and advanced configuration options. Features like Hot Swappable Power Supplies and Fans ensure minimal downtime during maintenance activities. Additionally, these switches come equipped with comprehensive features for network visibility and monitoring, including Cisco’s In-Service Software Upgrade (ISSU) capabilities that allow for continuous operations during updates.

Security is paramount in today’s networking landscape, and the Cisco 5000 Series is equipped with advanced security features. These include support for Virtual LANs (VLANs), Access Control Lists (ACLs), and advanced threat detection mechanisms. Cisco Identity Services Engine (ISE) integration provides granular control over user access and policy enforcement, creating a secure environment for sensitive data.

In summary, the Cisco Systems 5000 Series is a powerful solution designed for modern networking challenges, featuring hybrid deployment capabilities, robust performance metrics, high availability, and advanced security protocols. Businesses deploying these switches benefit from scalability and flexibility, ensuring their network can adapt to evolving demands while maintaining optimal performance and security.