Cisco Systems MGX 8220 Colocating Cisco Units in the Same Rack, Electrostatic Wrist Strap Kit

Page 166

Chapter

Rack-Mounting the MGX 8220 Units

the adhesive surface and attach the clip to the front of the unit above the ring lug. Mount the clip sideways to allow the strap to be held in a position that will not interfere with the removal of the number 1 card. Use the clip to store the strap when not in use. (See Figure 7-7.)

Figure 7-6 Electrostatic Wrist Strap Kit

Coiled cord

Snap

connection

Ring lug #10

Strap

Clip with adhesive back

H8279

Figure 7-7 Installed Wrist Strap Kit

Strap

Clip

Cord

Lug

Left front mounting

H8280

Colocating Cisco Units in the Same Rack

Different Cisco units, for example, MGX 8220 shelf, BPX switch, and ESP, can be colocated in the same rack or cabinet. When this is done, however, the inclusion and positioning of MGX 8220 power, cooling, booster, plenum, and spacer modules relative to the MGX 8220 shelf must be the same as those when the MGX 8220 shelf is used in a dedicated rack.

Some examples of multisystem configurations are shown in Figure 7-8.The configuration on the left includes a BPX switch, redundant ESPs and two MGX 8220 shelves. The configuration on the right includes a BPX switch and three MGX 8220 shelves.

In multisystem racks, the BPX switch, if included, should be mounted at the bottom. The MGX 8220 shelves including the power, cooling, booster, plenum, and spacer should be mounted in the proper order at the top to allow for growth.

 

Cisco MGX 8220 Installation and Configuration

7-12

Release 5.0, Part Number 78-6430-03 Rev. D0, November 2003

Image 166
Contents Cisco MGX 8220 Installation and Configuration Corporate HeadquartersPage FIC 04DU9-ISN Page Page Equipment Attachment Limitations Document Information General InformationMailing Information Business Reply Mail Organization Cisco WAN Switching Product Name ChangeAudience OverviewSpacer Unit Cooling Assembly Power Power Entry OptionsDC Power Drain and Circuit Protection Core Module OverviewT1 Backcards Service ConfigurationIntroduction Upgrading FirmwareLMI Interface Clearing Any Alarms Related to ds3VPI/VCI Mapping Unpacking PowerVertical Positioning Cabling Summary Dumb Terminal onto the Maintenance PortCabling for RJ-48 Connectors on T1 and E1 Ports A-5 T1 Cabling E1 CablingSpecifications B-1 FRSM-8E1 SpecificationIntroduction C-1 Service Interface T1/E1 Virtual Circuits Matm SpecificationUsing the Procedure Tables Finding the Right Procedure Virtual CircuitsResetsys Upgrade/Downgrade Save/Restore SM Configuration Resetsys or clrallcnfCompatibility C-46 Clrallcnf C-47 G U R E S Xviii Figure A-1 Figures Cisco MGX 8220 Installation and Configuration B L E S Table A-9 Objectives Cisco WAN Switching Product Name ChangeAudience Organization Chapter Title DescriptionRelated Documentation ConventionsWorld Wide Web Obtaining DocumentationDocumentation CD-ROM Documentation Feedback Obtaining Technical AssistanceOrdering Documentation Cisco.comTechnical Assistance Center Cisco TAC Web SiteCisco TAC Escalation Center Xxx Cisco MGX 8220 System Overview New in ReleaseA P T E R Configuration Examples Cisco BPX 8600 Series SwitchStandalone Cisco MGX 8220 Edge Concentrator Service InterfacesRemote Locations ATM UNI/NNIScalability Standards-Based Conversion to ATMATM Local Management Interface Traffic ManagementCisco MGX 8220 Shelf Cards Supported in the Cisco MGX Frame Service ModulesCisco MGX 8220 Cards Broadband Network ModulesATM UNI Service Modules Service Resource Modules Circuit Emulation Service ModulesInverse Multiplexing for ATM Trunk Modules Cisco MGX 8220 Management Release 5.0, Part Number 78-6430-03 Rev. D0, November Common Equipment Description OverviewCisco MGX 8220 Shelf Front View of the Cisco MGX 8220 Shelf with Cards Installed Cisco MGX 8220 BackplaneTypical Cisco MGX 8220 Hardware Weights Power Entry OptionsDC Powered Systems AC Powered Systems AC Power Assembly front without grillCooling Assembly DC Power Drain and Circuit ProtectionMain Cooling Assembly Cisco MGX 8220 Shelf ConfigurationPlenum Exhaust Chamber Booster Cooling AssemblyCooling Assembly Power Spacer UnitOptional Cisco-Supplied Cabinet Cisco MGX 8220 CabinetCore Module Overview 10 Cisco MGX 8220 Top Level Block Diagram Cisco MGX 8220 ASC Shelf Controller 11 ASC CardsConsole Ports Ethernet Transceiver ExtendersBroadband Network Modules ASC LED IndicatorsAuto Card Restore Type of LED Color Meaning of LEDBNM-T3/E3 ATM Trunk Interface 15 CC, FFCI, EFCI, Supv, PTI, and CLP Fields Push Buttons BNM-T3/E3 LED IndicatorsType of LED Color Meaning BNM-155 16 BNM-155 CardsATM Trunk Interface Back Card SMF-155 Back CardBNM-155 LED Indicators Service Resource Modules AX-SRM-T1/E1 FeaturesRules for Installation of SRMs 17 SRM-T1/E1 Card1N RED SRM-T1/E1 LED IndicatorsBert 18 AX-SRM-3T3 Cards Release 5.0, Part Number 78-6430-03 Rev. D0, November Summary of User Interface Connections Functions of the User InterfaceProtocols Physical ConnectionsBNM UI Function Physical Access Path TCP/IP Protocols Used User Interface Access PortsMaintenance Port Matrix of User Interface CombinationsMaintenance Port Access Control and LAN PortsControl Port Access In-Band Access LAN Port Access to the Cisco MGX 8220 ShelfAccounts PasswordsUser Accounts and Privilege Levels Privilege LevelsFollowing prompt appears Login Procedure Connecting Using the Maintenance PortConnecting a PC using the COM Port Connecting Using the Control PortConnecting a Terminal Server Connecting using an In-Band Connection Command-Line InterfaceConnecting using the LAN Port Cisco MGX 8220 Management Through Snmp Establishing the Cisco MGX 8220 to Cisco BPX ConnectionAxisSystem Structure of the MIBsCardGeneric CardSpecific AxisServicesAxisLines Tftp User Interface Upgrading FirmwareASC Frsm Ausm Cesm Frasm Imatm MIB Tftp destIPaddConfiguring Statistics Configuring and Collecting StatisticsCollecting Statistics Statistics Collection File Format Configuration Save and RestoreField Description Field Size Save Tftp Command Format Restore Tftp Command FormatRelease 5.0, Part Number 78-6430-03 Rev. D0, November MGX 8220 Service Modules IntroductionFrsm Connection Types Frame Relay Service Modules FRSMsFrame-Relay-to ATM Network Interworking NIW Congestion Indication BPX 8620 Network with Networking Interworking ConnectionsPVC Status Management Frame-Relay-to ATM Service Interworking SIWCell Loss Priority and Congestion Indication Command/Response Mapping Translation and Transparent Modes Frame ForwardingFrame-based User-to-Network Interface Funi Loss Priority IndicationFractional FRSMs FRSMs for T1 and E1 linesChannelized FRSMs Example of T1/E1 Frsm Front Cards AX-FRSM-HS1 and MGX-FRSM-HS1/B Features FRSMs for High Speed Serial LinesMGX-FRSM-HS2 Features Example FRSM-HS1 Front CardFrame Relay Access Service Module Stun ConnectionsUsing Frasm for a Stun Connection Bstun ConnectionsUsing Frasm for a Bstun Connection Fras ConnectionsUsing Frasm for a Fras BNN Connection Example Frasm Front Cards User Interface Frame Relay to ATM ConversionCell Loss Priority ATM UNI Service Module Ausm Cards Ausm LED Indicators AUSM-8T1/E1 AUSM-8T1/E1 LED Indicators Type of LED Color Description10 AUSM-8T1/E1 Front Card Inverse Multiplexer for ATM Trunk Module An illustration of the Imatm cards is provided in FigureIMATM-8E1 IMATM-8T1BNC SMB-E3E1Imatm LED Indicators HsportCircuit Emulation Service Modules Circuit Emulation Service Module 4-port14 Cesm Card Active LED Cesm 4-Port LED IndicatorsPort LED Standby LEDT1/E1 Unstructured Data Transfer Circuit Emulation Service Module 8-portT1/E1 Structured Data Transfer AX-SMB-8E1-LM AX-R-SMB-8E1-LM15 8-Port Cesm Cards Cesm 8-Port LED Indicators Back Cards Service Module Back CardsT1 Backcards DB15-4X.21-BCHssi Back Cards Redundancy Back CardsT1/E1 Backcards 17 T1/E1 Redundancy Back Cards Release 5.0, Part Number 78-6430-03 Rev. D0, November Setting up a Frame Relay Connection Via Cisco WAN ManagerVia the Command-Line Interface Frsm Network Interworking ConnectionsEstablish the Customer Equipment to BPX Segments Frame Relay Connection through an MGX 8220 and BPX NetworkEstablish the BPX-to-BPX Segment Parameter Description Frsm Service Interworking ConnectionsFuni and Frame Forwarding MCRAusm Connections ATM to-ATM Connection ScreenCesm Connections BPX-to BPX-SegmentFrasm Connections Fras BNN Connections Stun Connections Ffffffff Bstun Connections Chapter Frasm Connections Adding the Line Configuring Imatm ConnectionsDownload procedure Sample DisplayChecking the Alarms on a ds1 Line Clearing Any Alarms Related to ds3LineNum LineAlarmState Plcp Configuration for ds3 Sample OutputExample Configuring the Clock SourceEND a END B Stratum 1/2 Add the Channel Route Entry Commands Related to AIM GroupConfigure the AIM Group AddchrteDisplay the AIM Group UNIConfiguring the Port Queue Sample DataDisplay the Port Counters Dspportcnt Aimgrp noRelease 5.0, Part Number 78-6430-03 Rev. D0, November Using the Command-Line Interface MGX 8220 in Stand-alone ApplicationsOut-of-Band Access Configuring the BNMLMI Interface Setting Trap Managers VPI/VCI MappingInterface Type VC ConnectionsVP Connections UNI NNIProvisioning Frsm Channels Provisioning Ausm ChannelsChapter Provisioning Ausm Channels Installation and Start-Up Safety RecommendationsMaintaining Safety with Electricity GroundingSite Preparation PowerRack Space Unpacking CoolingRack-Mounting the MGX 8220 Units Parts ChecklistUnpacking Each Container Horizontal Positioning Vertical PositioningCooling Configuration Guidelines Rack-Mounted MGX 8220-One- and Two-Shelf Configurations17.750 Minimum Plenum or spacer Or 2 U Rack-Mounting the Modules Use the Angle Bracket to Secure the Module to the RackLimited Access Center MountRack-Mounting the Plenum or Spacer Mounting the Electrostatic Wrist StrapColocating Cisco Units in the Same Rack Electrostatic Wrist Strap KitConnecting Power for DC Systems DC Power to the Shelf10 PEM Cable Clamp DC Power to the Fan Cooling Assembly 11 DC Power Cabling for One-Shelf and Two-Shelf Racks12 DC Cabling for Three-Shelf and Four-Shelf Racks Available Power Connecting Power for AC SystemsAC Input Power Monitoring Power Supply Status13 AC Power Assembly Block Diagram 14 AC Cabling for One-Shelf and Two-Shelf Racks 15 AC Cabling for Three-Shelf and Four-Shelf Racks Plenum Chamber Kit Cable ManagementDescription Quantity Main Cooling and Booster Cooling Kit 16 Cable Management Kit on the Plenum ChamberCable support, attach with 10-32 thread forming screws Power Cable Routing Cable Routing19 Routing Power Cables at the Cooling Assembly Routing Data CablesRemoving and Installing the Front Cards Readying the CardsRemoving and Installing the Back Cards 22 Connecting BNM-T3 or BMN-E3 Cables Making the BNM Trunk ConnectionMaking the Service Interface Connections 23 Cabling for Redundant BNM CardsMaking External Clock Connections Alarm Output ConnectionDumb Terminal onto the Maintenance Port Attaching a Control ConsoleInitial Configuration Initial Start-Up of the MGX 8220 ShelfStep Preventive Maintenance Troubleshooting the MGX 8220 ShelfSymptom Probable Cause Remedy General Troubleshooting ProceduresASC Fail LED Procedure for All Errors DspcdsDisplayed Log Message Format Dsplog slot# slot# day offsetASC Log Codes Error Number Display Log String Detail DescriptionLog Codes Log Code Range Module Logging MessagesError Number Display Log String Detail Description Null Error Number Display Log String Detail Description Error Number Display Log String Detail Description Error BNM Log Codes Error Number Display Log String Detail Description Fwready = SRM Log Codes Bram Ausm Log Codes PDU Error Number Display Log String Detail Description Error Number Display Log String Detail Description Replacing Parts Replacing a Front Card Replacing a Back CardReplacing a DC Power Entry Module Chapter Replacing Parts Release 5.0, Part Number 78-6430-03 Rev. D0, November Connector Description Imatm T1/E1 ConnectorsT3 Trunk Cabling Cable Parameter Description Frame Relay CablingT1 Cabling Pin No DescriptionDB-15 Connector BNC ConnectorE1 Cabling Pin No Name Signal Function Polarity Signal Source Port ConnectorsHssi Port Connectors DTECabling for RJ-48 Connectors on T1 and E1 Ports DC Power Cabling Figure A-2 RJ-48 ConnectorsControl and Clock Cabling AC Power CablingMaintenance and Control Ports Pin No Name Source DescriptionDSR DCE Modem CableExternal Clock Input Cabling DTR DTEE1 Clock Cabling T1/E1 Clock CablingPin No. Description External Alarm Cabling Pin No Alarm DescriptionModel No Description Usage Standard MGX 8220 CablesRedundancy Y-Cables Cable Used OnRelease 5.0, Part Number 78-6430-03 Rev. D0, November BNM-T3 Specification Intershelf LinkCard General BNM-T3 PlcpLCV, LES, %EFS, LSES, SEFS, PCV, PES, PSES, SEFS, UAS BNM-E3 SpecificationCcitt Card General Common Specifications BNM-155 SpecificationsIntershelf Link Specifications SMF Specific SpecificationsGeneral Card Specifications ASC Specification SRM-T1/E1 Specification BNC-3T#FRSM-4T1 Specification Service InterfaceSystem Interface Virtual Circuits Card General FRSM-4E1 Specification Transmit frames S Virtual Circuits ATM cells Number of cells transmitted to BNM FRSM-8T1 Specification Appendix B Specifications FRSM-8T1 Specification Release 5.0, Part Number 78-6430-03 Rev. D0, November FRSM-8E1 Specification ATM Layer Per Ccitt I.361 and ATM UNI Virtual Circuits ATM cells Number of cells transmitted to BNM Errors and Alarm Handling FRSM-HS2 SpecificationExternal Interface Specification FRSM-HS2 Line Statistics and Counters SpecificationsCounters per line Statistics Service Interface E1 Ausm Specification 4 PortService Interface T1 LCV, LES, LSES, CV, ES, SES, SEFS, AISS, UASCBR, VBR, VBR+ ATM InterfaceVPI/VCI PCR, SCR VBR, Ccdv CBRCard General Service Interface T1/E1 CESM-4T1/E1 SpecificationESD AAL1 Physical Layer Interface T1 Matm SpecificationSMB-E3E1-LM Physical Layer Interface T3 Physical Layer Interface E1LOS, OOF, AIS, RDI Physical Layer Interface E3 AIM Groups and LinksCard General Release 5.0, Part Number 78-6430-03 Rev. D0, November Firmware Upgrade and Downgrade Procedures Using the Procedure Tables Std. Upgrade Std. Downgrade Core Card Set From Rel ViaFinding the Right Procedure Standard Upgrade and Downgrade ProceduresProcedure 1-Standard Upgrade, 1-Core Card Set Enter the tftp put ASCFWfile AXISASCACTIVE.FW commandProcedure 2-Standard Downgrade, 1-Core Card Set Enter the tftp put SMFWfile AXISSM1$slot.FW commandProcedure 3-Standard Upgrade, 2-Core Card Set Enter the tftp put ASCFWfile AXISASCSTANDBY.FW command Procedure 4-Standard Downgrade, 2-Core Card Set Enter the tftp put ASCFWfile AXISASCACTIVE.FW command Procedure 5-Standard Upgrade, 1-Core Card Set Procedure 6-Standard Upgrade, 2-Core Card Set Enter the tftp put SMFWfile AXISSM1$slot/0.FW commandEnter the tftp put ASCFWfile AXISASCSTANDBY.FW command Procedure 7-Standard Downgrade, 1-Core Card Set Enter the tftp put SMBTfile AXISSM1$slot.BOOT commandProcedure 8-Standard Downgrade, 2-Core Card Set Enter the tftp put SMFWfile AXISSM1$slot.BOOT commandEnter the tftp put SMBTfile AXISSM!$slot.BOOT command Procedure 9-Standard Upgrade, 1-Core Card Set Procedure 10-Standard Upgrade, 2-Core Card Set Procedure 11-Standard Downgrade, 1-Core Card Set Step Procedure 12-Standard Downgrade, 2-Core Card Set Graceful Upgrade and Downgrade Procedures Procedure 13-Graceful Upgrade, 1-Core Card Set SM only Procedure 14-Graceful Downgrade, 1-Core Card Set SM only Procedure 15-Graceful Upgrade, 2-Core Card Set Enter the tftp put SMBTfile AXISSM1$slot.FW command Procedure 16-Graceful Downgrade, 2-Core Card Set Enter the tftp put SMFWfile AXISSM1$sl26 command Procedure 17-Graceful Upgrade, 1-Core Card Set SM only Procedure 18-Graceful Downgrade, 1-Core Card Set SM only Enter the tftp put SMBTfile AXISSM1$slot.FW command Procedure 19-Graceful Upgrade, 2-Core Card Set Procedure 20-Graceful Upgrade, 2-Core Card Set Release 5.0, Part Number 78-6430-03 Rev. D0, November Procedure 21-Graceful Upgrade, 2-Core Card Set Enter the tftp put SMBTfile AXISSM1$slot.FW command Procedure 22-Graceful Downgrade, 1-Core Card Set SM only Procedure 23-Graceful Upgrade, 2-Core Card Set Enter the tftp put SMBTfile AXISSM1$slot.BOOT command Procedure 24-Graceful Downgrade, 1-Core Card Set SM only Procedure 25-Graceful Upgrade, 2-Core Card Set Enter the tftp put SMBTfile AXISSM1$slot.BOOT command Description of Upgrade/Downgrade Terminology File Size Tftp putASC.FW Dspfwrevs Slot-Specific and Card-Type-Specific SM FirmwareSoftswitch ResetsysFlashStartAddr and flashEndAddr Dsptotals DonotupdatestandbyDspadrxlat CompatibilityUpgrade/Downgrade Resetsys or clrallcnfSave/Restore ASC Configuration ClrallcnfSave/Restore SM Configuration D E See CWM ASC BNMFirmware, upgrades Firmware Media Kit CWMASC Ausm PEMHssi SIWSnmp FRSM-HS2 B-24 Tftp
Related manuals
Manual 6 pages 22.38 Kb

MGX 8220 specifications

The Cisco Systems MGX 8220 is a versatile, high-performance media gateway that has become an integral component in the telecommunications infrastructure. Designed to facilitate the transition from traditional circuit-switched networks to advanced packet-switched environments, the MGX 8220 supports a wide array of voice, video, and data services, making it an essential tool for service providers and enterprises seeking to enhance their network capabilities.

One of the key features of the MGX 8220 is its robust signaling and media processing capabilities. Equipped with support for both Voice over IP (VoIP) and traditional telephony protocols, this gateway enables seamless integration of different communication formats. It boasts a modular architecture, which allows for the addition or removal of various line cards to meet changing demands and technology advancements. This modularity provides operators with the flexibility to scale their services without significant overhauls to their existing infrastructure.

The MGX 8220 is capable of delivering high-density media handling for a multitude of services. With its support for ATM and IP networks, the gateway can handle TDM (Time-Division Multiplexing) to packet voice conversions efficiently. It is designed to optimize network resources by dynamically allocating bandwidth based on traffic requirements, thus ensuring efficient use of network resources and improved performance.

Another significant characteristic of the MGX 8220 is its enhanced quality of service (QoS) features. This capability ensures that voice and video traffic is prioritized appropriately, minimizing latency and jitter while maximizing overall call quality. By employing sophisticated traffic management techniques, the MGX 8220 can deliver a superior user experience, which is critical for any service provider aiming to offer competitive communication solutions.

Furthermore, the gateway includes built-in security features to protect against unauthorized access and ensure the integrity of sensitive data. This includes encryption for voice and video transmission, as well as support for secure signaling protocols.

Overall, the Cisco Systems MGX 8220 stands out as a comprehensive media gateway solution, providing essential functionalities for modern communication needs. Its combination of modularity, high-density processing, effective QoS management, and security features makes it a compelling choice for organizations looking to modernize their telecommunications infrastructure while ensuring reliability and performance. As businesses continue to evolve and demand more from their networks, the MGX 8220 offers a pathway to future-ready communications.