White Rodgers 1050 Dial Settings Cont, D. Additional Information, Chart 1 - Round Dial Set at “N”

Models: 1050

1 10
Download 10 pages 50.04 Kb
Page 5
Image 5
D.ADDITIONAL INFORMATION:

D.ADDITIONAL INFORMATION:

Charts 1, 2, and 3 show the effect which dial settings have upon boiler water temperature under varying outside air temperatures. Some examples of how these charts may be used are as follows:

Example 1 (See Chart 1) – To determine boiler water tempera- ture for 10° outside air temperature and a #3 square dial setting, move up on 10° line until it intersects the heavy line for a #3 square dial setting. Then move horizontally to left and read water temperature of 150°.

Example 2 (See Chart 1) – To determine square dial setting for desired boiler water temperature of 210° at -20°outside temperature, move up on -20°line to 210°. Since the heavy line for a #4 square dial setting intersects at this point, the square dial should be set at 4.

Example 3 – Note the effect of changing setting of the round dial from “N” (Chart 1) to 4 divisions “warmer” than “N” (Chart 3). Water temperature has been increased 20° for all outside temperatures.

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

3

 

(116)

240

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

1

 

(104)

220

 

 

 

 

 

 

 

 

 

(93)

200

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(82)

180

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

(71)

160

3

 

 

 

 

 

 

 

 

(60)

140

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(49)

120

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(38)

100

 

 

 

 

 

 

 

 

 

(27) 80

 

 

 

 

 

 

 

 

 

°C °F

 

 

 

 

 

 

 

 

 

 

-20

-10

0

10

20

30

40

50

60

70°F

 

-29

-23

-17

-12

-7

-1

4

10

16

21°C

Chart 2 — Round Dial Set 2 divisions “COOLER” than “N”.

DIAL SETTINGS CONT.

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

3

 

(116)

240

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

1

 

(104)

220

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(93)

200

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(82)

180

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(71)

160

 

 

 

 

 

 

 

 

N

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(60)

140

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(49)

120

 

 

 

 

 

 

 

 

 

(38)

100

 

 

 

 

 

 

 

 

 

(27) 80

 

 

 

 

 

 

 

 

 

°C °F

 

 

 

 

 

 

 

 

 

 

-20

-10

0

10

20

30

40

50

60

70°F

 

-29

-23

-17

-12

-7

-1

4

10

16

21°C

Chart 1 — Round Dial Set at “N”

(127)

260

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

3

 

(116)

240

5

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

1

 

(104)

220

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(93)

200

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(82)

180

2

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(71)

160

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(60)

140

 

 

 

 

 

 

 

 

 

(49)

120

 

 

 

 

 

 

 

 

 

(38)

100

 

 

 

 

 

 

 

 

 

(27) 80

 

 

 

 

 

 

 

 

 

°C °F

 

 

 

 

 

 

 

 

 

 

-20

-10

0

10

20

30

40

50

60

70°F

 

-29

-23

-17

-12

-7

-1

4

10

16

21°C

Chart 3 — Round Dial Set 4 divisions “WARMER” than “N”.

5

Page 5
Image 5
White Rodgers 1050 Dial Settings Cont, D. Additional Information, Chart 2 - Round Dial Set 2 divisions “COOLER” than “N”