INSTALLATION
Both the outdoor bulb and inside bulb should be installed before the control case, since capillary lengths of these bulbs will normally determine the final location for the control case.
NOTE
Use care not to bend or dent either of the sensing bulbs
ROOF
A. INSTALLING THE OUTDOOR BULB:
Locate the outdoor bulb so that it senses actual outdoor air temperature. Attach mounting bracket supplied with control to some convenient outside part of the building so that the outdoor bulb is:
1.Exposed to circulation of air and wind.
2.Shielded from rain, snow, and direct rays of sun.
3.Not close to false sources of heat such as dryer vents, exhaust fans, melting snow or ice, etc.
4.Sufficiently above ground to prevent tampering or being covered with snow, ice, or debris.
B. INSTALLING THE WATER BULB:
The water bulb should be installed in a hot section of the boiler. It should never be installed near a return inlet to the boiler.
C. INSTALLING THE CONTROL CASE:
The case of the
1.Install it on a vertical surface such as a wall or the side of a joist.
2.Do not install it on a heated surface such as on the boiler or a hot water pipe.
3.Install it high enough so that it will be convenient to make adjustments on round dial and large screw at bottom of case.
4.Install it so end of case with electrical outlet is on top.
CEILING
The underside of the eaves or overhang of a NORTH or NORTHWEST roof is normally a good location. It should be exposed to the circulation of air and wind.
INSTALLED
ON JOIST
INSTALLED
HIGH ON WALL
MOUNTING
BRACKET
OUTDOOR BULB
WIRING & OPERATION
All wiring should be done in accordance with local and national electrical codes and ordinances.
This
INDOOR
OUTDOOR
CONTROL
HOT WATER BOILER
HIGH LIMIT
CONTROL
ROOM THERMOSTAT
RELAY
BURNER
CIRCULATOR
2