White Rodgers 1050 Dial Settings, A. Setting The Round Dial, B. Setting The Square Dial

Models: 1050

1 10
Download 10 pages 50.04 Kb
Page 4
Image 4
DIAL SETTINGS

DIAL SETTINGS

When using this control as an exact replacement, use same dial settings as for old control.

A.SETTING THE ROUND DIAL:

Set the round dial for “N” initially. This will enable minor additional adjustments to be made later if the specific instal- lation should require it (refer to “C”.)

B.SETTING THE SQUARE DIAL:

Select the proper square dial setting from table 1 or 2 below. For the majority of installations, the dial setting selected should provide satisfactory boiler operation without requiring any further dial adjustments. When required, additional adjustments may be made as explained in “C”.

OUTDOOR

 

 

 

 

 

 

 

DESIGN

 

SUGGESTED SQUARE DIAL SETTING

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20°F (-7°C)

3

 

4.5

--

--

--

--

 

 

 

 

 

 

 

 

10°F (-12°C)

2.5

 

3.5

5

--

--

--

 

 

 

 

 

 

 

 

0°F (-17°C)

2

 

3

4

5

--

--

 

 

 

 

 

 

 

 

-10°F (-23°C)

1.5

 

2.5

3.5

4.5

5

--

 

 

 

 

 

 

 

 

-20°F (-29°C)

1

 

2

3

4

4.5

5

 

140

160

180

200

220

240

 

(60)

(71)

(82)

(93)

(104)

(116)

 

BOILER DESIGN TEMPERATURE °F (°C)

 

 

 

 

 

 

 

 

 

SQUARE DIAL

Adjusts for heat-loss of specific installation

ROUND DIAL Adjusts comfort level required

Adjustment screw

for changing setting

of square dial

Table 2 shows suggested square dial settings for various reset ratios. The first number of the reset ratio refers to the outdoor bulb, the second number refers to the inside bulb. For 1-1/2 to 1 ratio, for example, each 1-1/2°F drop in outdoor temperature will cause a 1°F increase in boiler water.

Reset Ratio

Suggested Square

 

Dial Setting

 

 

1.5 to 1

1

 

 

1 to 1

2.5

 

 

1 to 1.5

4.5

 

 

C.ADDITIONAL ADJUSTMENTS:

If, due to system variables such as heat loss of building, boiler size, etc., the square dial setting selected in “B” does not give desired boiler temperatures, additional adjustments may be made as follows:

Round Dial – One division change in the round dial setting changes boiler water temperature about 5° at all outdoor temperatures.

Square Dial – Changing the square dial setting 1/2 division (3 full revolutions of adjusting screw) changes boiler water temperature about 10° at low outdoor temperatures (0° to -20°)

CONDITION

SUGGESTED ADJUSTMENT

 

 

Area too cool at low

Raise square dial setting.

outdoor temperatures.

 

 

 

Area too warm at low

Lower square dial setting.

outdoor temperatures.

 

 

 

Area too cool at all

Raise round dial setting. (Also

outdoor temperatures

raise square dial setting if round

 

dial has been set to “warmest”

 

setting.)

 

 

Area too warm at all

Lower round dial setting. (Also

outdoor temperatures

lower square dial setting if

 

necessary.)

 

 

4

Page 4
Image 4
White Rodgers 1050 Dial Settings, A. Setting The Round Dial, B. Setting The Square Dial, C. Additional Adjustments