Moving System Components
Step 13 To secure the
To secure the
Warning When stranded wiring is required, use approved wiring terminations, such as
Warning The illustration shows the DC power supply terminal block. Wire the DC power supply using the appropriate lugs at the wiring end, as illustrated. The proper wiring sequence is ground to ground, positive to positive (line to L), and negative to negative (neutral to N). Note that the ground wire should always be connected first and disconnected last. (For translations of this safety warning, refer to the section “DC Power Supply Wiring Warning” on page 45.)
Step 14 Place the terminal block cover over the terminal block and secure it with the two captive installation screws. (See Figure 11.)
Figure 11 DC-Input Power Supply Cable Connections
DO NOT SHIP WITH POWER SUPPLY
INSTALLED
OUT
INPUTFAIL
POWER
INPUT VOLTAGE :
INPUT CURRENT :
FASTENER TO BE FULLY ENGAGED BEFORE OPERATING POWER SUPPLY
Captive installation screw
Power leads attached to terminal block
( ) negative ( ) positive () ground
Nylon ties on cable and metal bracket
H2530
Step 15 Connect the opposite end of each power cable to an appropriate power source.
Caution Do not turn on any power supplies until you are ready to power up the system. The interlock switch that locks the power supply in the slot also turns on the system power.
Step 16 Proceed to the section “Verifying the Installation” on page 24 to apply power and check the installation.
Cisco 7000 and Cisco 7507 Chassis Replacement Instructions 23