Cisco Systems uBR7246VXR quick start Tools, Disconnected last. Statement

Page 17

Tools

8-mm wrench or nut driver, or adjustable wrench (for connecting a grounding lug to a DC-input power supply only)

7-mm wrench or nut driver, or adjustable wrench (for connecting the DC-input power lead strain-relief cover to a DC-input power supply only)

14 AWG (2.08 mm2) cable with a minimum of three conductors rated for at least 140 ° F (60° C) (for DC-input power supply installations only)

Standard wire stripper

Step 1 Ensure that the –48V and +48V leads are disconnected from the power source.

Step 2 At the rear of the router, check that the power switch on the power supply is in the OFF (0) position.

Step 3 Connect the two-hole grounding lug on the ground wire to the M5 grounding receptacles with the two M5 nuts. Tighten the nuts using an 8-mm wrench or nut driver (or adjustable wrench). See Figure 12.

Step 4 Using a wire stripper, strip approximately 0.55 inch (14 mm) from the –48V and +48V leads.

Step 5 Insert the stripped end of the +48V lead all the way into the +48V lead receptacle and tighten the receptacle screw using a 3/16-inch flat-blade screwdriver. Repeat for the –48V lead.

Step 6 Make sure that the entire stripped end of each lead is inserted all the way into its receptacle. If any exposed wire at the stripped end of a lead is visible after inserting the lead into its receptacle, remove the lead from the receptacle, use the wire stripper to cut the stripped end of the lead, and repeat Step 4 and Step 5.

Step 7 After tightening the receptacle screws and nuts for the ground, +48V, and –48V DC-input leads, run the +48V and –48V leads between the two strain-relief studs on the power supply faceplate. (See Figure 12 on page 18.)

Step 8 Install the strain-relief cover over the +48V and –48V leads and secure the cover to the strain-relief studs using the two M4 nuts with a 7-mm wrench or nut driver (or adjustable wrench). (See Figure 12.)

Step 9 Connect the ground wire, +48V lead, and –48V lead to the power source.

Caution Each DC-input power supply has an electrical current rating of 14 A, 700 VA. Use a minimum of 14 AWG (2.08 mm2) wire for the input to each DC-input power supply. The power input must be protected by a 20 A circuit breaker or fuse that is in compliance with your local electric regulations.

Warning

The illustration shows the DC power supply terminal block. Wire the DC power supply using the appropriate wire

 

terminations at the wiring end, as illustrated. The proper wiring sequence is ground to ground, positive to positive

 

(line to L), and negative to negative (neutral to N). Note that the ground wire should always be connected first and

 

disconnected last. Statement 61

 

 

17

Image 17
Contents Cisco uBR7246VXR Universal Broadband Router Duration of Hardware Warranty Cisco One-Year Limited Hardware Warranty TermsReplacement, Repair, or Refund Policy for Hardware To Receive a Return Materials Authorization RMA NumberStatement OverviewCisco uBR7246VXR Components Front and Rear Chassis Views Card Slot and Logical Interface NumberingTemperature and Humidity Requirements Power GuidelinesSpecification Minimum Maximum Site PreparationIEC 60950 based safety standards. Statement Power Connection Guidelines for DC-Powered SystemsCabling Guidelines Ethernet and Fast Ethernet ConnectionsRack-Mount Installation Guidelines Installing the ChassisWorkbench and Tabletop Installation Guidelines Installation Tools and EquipmentAttaching the Rack-Mount Brackets Verifying Contents After UnpackingAttach the Rack-Mount Brackets to the Front of the Chassis Attach the Rack-Mount Brackets to the Rear of the ChassisAttach the Rack-Mount Brackets to the Middle of the Chassis Location of Cable Management Bracket Installing the Cable-Management BracketsInstalling the Chassis in the Rack Use copper connectors only. Statement Installing the Chassis on a Workbench or TabletopConnecting the Chassis to Ground Page AC and DC Power Supplies Connecting the Chassis to PowerDC Power Supplies AC Power SuppliesDisconnected last. Statement ToolsCabling Replacing the Strain-Relief Cover on a DC-Input Power SupplyPowering on the Cisco uBR7246VXR Router Page Identify Startup Problems Troubleshooting the InstallationOther Troubleshooting Information Websites Related Documentation Obtaining Documentation and Submitting a Service Request