Tripp Lite 3-Phase 30kVA Operation Special Conditions, Operation on BYPASS-VOLTAGE OUT of Range

Page 9

Operation (Special Conditions)

OPERATION ON BYPASS—VOLTAGE OUT OF RANGE

While in Bypass Mode, the UPS monitors the input voltage, which on Bypass equals the output voltage. If the output voltage passes out of an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying output power to its load. If power levels return to an acceptable level, the UPS resumes supplying power to the load, and its LCD reports that output voltage was too high or too low at one time, but has returned to nominal.

Bypass Voltage Condition

LCD Display Message

 

 

>15% Higher than Nominal

BYPASS HI NO O/P

 

 

>20% Lower than Nominal

BYPASS LO NO O/P

Was Too High, Now Nominal

BYPASS WAS HI

 

 

Was Too Low, Now Nominal

BYPASS WAS LO

 

 

INVERTER ON WARNINGS

When the inverter is ON, the LCD Display may show any one of the following warnings:

Condition

LCD Display Message

 

 

UPS Output Overload

OVERLOAD 110%

 

 

UPS Charger Failure

CHARGER FAILURE

 

 

Abnormal Input Frequency

FREQUENCY ERROR

 

 

Abnormal Input Phase

PHASE ABNORMAL!

 

 

Battery is Depleting*

ON BATTERY

 

 

Battery Charge is Nearly Depleted*

BATTERY LOW

 

 

* During a prolonged blackout, users should save files and shut down connected equipment.

The “BATTERY LOW” message indicates the UPS's batteries are nearly out of power and UPS shut down is imminent.

OPERATION UNDER SHUTDOWN

Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: For all conditions, the “Input,” “Output” and “Bypass” LEDs will be illuminated.

Condition

LCD Display Message

 

 

Overload Shutdown

ON BYPASS

 

OVERLOAD 150%

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

UPS Output Short Circuit

ON BYPASS

 

SHORT CIRCUIT!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Overtemperature

ON BYPASS

 

HIGH TEMP!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

DC BUS Overvoltage

ON BYPASS

 

DC BUS O.V.P.!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

DC BUS Failure

ON BYPASS

 

DC BUS FAIL!

 

SHUTDOWN...

 

VERSION: XXXXXXX

Condition

LCD Display Message

 

 

R/S/T Inverter Output Failure

ON BYPASS

 

R OUTPUT FAIL!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Low Battery

BYPS OFF NO O/P

 

LOW BATTERY!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Remote Shutdown

BYPS OFF NO O/P

 

REMOTE SHUTDOWN

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Emergency Stop

BYPS OFF NO O/P

 

EMERGENCY STOP!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

9

Image 9
Contents Español Français UPS Location Warnings Important Safety WarningsControl Panel Front PanelBattery Access Panel cover removed Rear Panel Rear PanelMounting Bracket Installation InstallationUPS Input and Output Hardwire Connection UPS LocationWiring Connection Initial Battery ChargingOperation Normal Conditions Output Voltage Selection VIA SoftwareSelf Testing Battery OK DC to DC OK Inverter Test SELF-TESTINGTurning the UPS OFF LCD Display Select ButtonOperation on BYPASS-VOLTAGE OUT of Range Operation Special ConditionsInverter on Warnings Operation Under ShutdownCommunications DRY Contact Interface Remote Emergency Power OFF EPODRY Contact Interface Table OpenBattery Packs are Heavy Do not Remove Battery SleeveCheck Battery Pack Voltage Before Completing Installation Adding or Replacing Internal BatteriesInternal Battery Pack Wiring Diagram Adding or Replacing Internal Batteries Adding or Replacing Internal Batteries Adding or Replacing Internal Batteries Warranty ServiceLimited Warranty Observe Proper PolarityModel SU20K3/3INT SpecificationsModel SU30K3/3INT Manual del Propietario Advertencias sobre la colocación y ubicación del UPS Advertencias de Seguridad ImportantesPanel DE Control Panel FrontalPanel DE Acceso a LA Bateria Tapa Removida Panel Frontal continuaciónPanel Trasero Panel TraseroUbicación DEL UPS InstalaciónInstalacion DE LOS Soportes DE Montaje Conexion a TierraCarga Inicial DE LA Bateria Operación Condiciones NormalesSeleccion DEL Voltaje DE Salida VIA Software Encendiendo EL UPSApagando EL UPS Operación Condiciones Normales continuaciónAUTO-PRUEBA Boton Select Seleccionar DE LA Pantalla LCDOperacion EN DERIVACION-VOLTAJE Fuera DE Rango Operación Condiciones EspecialesAdvertencias DEL Inversor Encendido Operacion Bajo CIERRE/PARADAComunicaciones Operación Condiciones Especiales continuaciónInterfaz DEL Contacto Seco Comunicaciones continuaciónApagado DE Emergencia Remoto EPO Tabla DE LA Interfaz DE Contacto SecoAñadiendo o Remplazando las Baterías Internas ¡NO Remueva LA Cubierta Protectora DE LA Bateria¡LOS Modulos DE Bateria SON Pesados Añadiendo o Remplazando las Baterías Internas continuación Diagrama DEL Cableado DEL Modulo DE Baterias InternasAñadiendo o Remplazando las Baterías Internas continuación Terminales ¡PELIGRO Garantía ServicioGarantia Limitada ¡OBSERVE LA Polaridad CorrectaModelo SU20K3/3INT EspecificacionesModelo SU30K3/3INT Especificaciones continuaciónManuel du propriétaire Mises en garde relatives à la localisation de londuleur Importantes consignes de sécuritéPanneau avant Panneau DE CommandePanneau Daccès AUX Batteries carter enlevé Panneau avant suitePanneau Arrière Panneau arrièreMises EN Garde Relatives À LA Localisation DE Londuleur IL Faut Installer Londuleur À Laide DE Brides DE FixationConnexion DE Mise À LA Terre Sélection DU CâblageFonctionnement Conditions normales Installation suitePremière Charge DE LA Batterie Sélection DE LA Tension DE Sortie À Laide DUN LogicielArrêter Londuleur Fonctionnement Conditions normales suiteÉxécution DUN AUTO-TEST Bouton DE Sélection DE Lécran ACLFonctionnement EN DÉRIVATION-TENSION Hors Plag Fonctionnement Conditions spécialesMises EN Garde Inverseur EN Marche Fonctionnement Pendant UN ArrêtFonctionnement Conditions spéciales suite Commuter Londuleur EN Mode NormalFonctionnement DU Commutateur DE Dérivation Manuelle Interface RS-232Arrêt Durgence Emergency Power OFF EPO À Distance Ajout et remplacement des batteries internesCommunications suite Interface Contact SECSchéma DU Câblage Interne DUN Bloc DE Batterie Ajout et remplacement des batteries internes suiteAjout et remplacement des batteries internes suite Bornes Ajout et remplacement des batteries internes suite Garantie Garantie Limitée À VIEObserver LA Bonne Polarité Modèle SU20K3/3INT SpécificationsModèle SU30K3/3INT Spécifications suite

3-Phase 30kVA specifications

The Tripp Lite 3-Phase 30kVA is a robust power protection solution designed for demanding environments, such as data centers, industrial facilities, and large commercial spaces. This uninterruptible power supply (UPS) is engineered to deliver reliable and consistent power while safeguarding sensitive equipment from power fluctuations and outages, making it an ideal choice for businesses that require uninterrupted operations.

One of the main features of the Tripp Lite 3-Phase 30kVA UPS is its ability to provide a high power output of 30,000 VA, which translates to significant flexibility in powering multiple devices and systems simultaneously. This capacity is critical for operations that rely on extensive and mission-critical equipment, ensuring that everything continues to run smoothly even in the event of utility power failure.

The UPS is equipped with advanced technologies designed to enhance its performance. The double-conversion online design ensures that your connected equipment receives clean, stable, and filtered power. This technology isolates sensitive electronics from typical power issues such as surges, sags, and electrical noise, minimizing the risk of damage. Furthermore, the unit features a high-efficiency mode that reduces energy consumption, resulting in lower operating costs and environmental impact.

The Tripp Lite 3-Phase 30kVA UPS also comes with comprehensive monitoring and management capabilities. Its intelligent LCD interface provides real-time information on input/output voltage, battery status, and system configuration, allowing administrators to monitor the UPS easily and make informed decisions regarding power management. Additionally, it supports SNMP compatibility for remote management via a network, enabling IT teams to efficiently oversee power and UPS status from a distance.

Another notable characteristic is the UPS's scalable design, which allows for multiple units to be combined to create a highly efficient power system tailored to the specific needs of the facility. This scalability ensures that the power infrastructure can evolve with growing demands without requiring a complete overhaul.

Overall, the Tripp Lite 3-Phase 30kVA UPS stands out as a reliable, efficient, and user-friendly solution for organizations seeking to enhance their power protection strategy. With its high capacity, advanced technologies, and comprehensive management features, it is well-equipped to support critical operations and ensure business continuity in a world where power integrity is paramount.