Tripp Lite BC Personal, BC Internet specifications Storage & Service, Specifications

Page 6

Storage & Service

Storage

First turn your UPS OFF and disconnect its power cord from the wall outlet. Then disconnect all equipment to avoid battery drain. If you plan on storing your UPS for an extended period of time, fully recharge the UPS batteries once every three months by plugging the UPS into a live AC outlet and letting the UPS charge for 4 to 6 hours. If you leave your UPS batteries discharged for an extended period of time, they will suffer a permanent loss of capacity, leaving your UPS unable to provide adequate protection.

Service

Before returning products for service, contact Tripp Lite customer support. If returning your UPS to Tripp Lite, please carefully pack the UPS using the ORIGINAL PACKING MATERIAL that came with the unit. Enclose a letter describing the symptoms of the problem. If the UPS is within the 2 year warranty period, enclose a copy of your sales receipt.

Specifications

 

BC Personal 200

BC Personal 300

Output Capacity (VA/Watts):

200/125

300/175

Battery Runtime (Half Load/Full Load) Minutes:

28/10

17/5

Battery Recharge Time:

2-4 hrs

2-4 hrs

Approvals:

UL, cUL, NOM

UL, cUL, NOM

Modem/Fax Protection

_

_

(Starting at 260V)

 

 

 

BC Personal 450

BC Internet 300

Output Capacity (VA/Watts):

450/280

300/175

Battery Runtime (Half Load/Full Load) Minutes:

17/5

17/5

Battery Recharge Time:

2-4 hrs

2-4 hrs

Approvals:

UL, cUL, NOM

UL, cUL, NOM

Modem/Fax Protection

_

1 line

(Starting at 260V)

 

 

 

BC Internet 400

BC Internet 500

Output Capacity (VA/Watts):

400/250

500/280

Battery Runtime (Half Load/Full Load) Minutes:

17/5

17/5

Battery Recharge Time:

2-4 hrs

2-4 hrs

Approvals:

UL, cUL, NOM

UL, cUL, NOM

Modem/Fax Protection

2 lines

2 lines

(Starting at 260V)

 

 

ALL MODELS:

Input Voltage/Frequency (120V/60 Hz); On Battery Output Voltage Range (120V +/- 5%); Output Waveform Line Mode (filtered sine wave); Output Waveform Battery Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A & B standards); AC Noise Attenuation (>40 dB); AC Protection Modes (H to N, H to G, N to G)

FCC Part 68 Notice (U.S. only)

If your Modem/Fax Protection causes harm to the telephone network, the Telephone Company may temporarily discontinue your service. If possible, they will notify you in advance. If advance notice isn’t practical, you will be notified as soon as possible. You will be advised of your right to file a complaint with the FCC. Your telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the proper operation of your equipment. If it does, you will be given advance notice to give you an opportunity to maintain uninterrupted service. If you experience trouble with this equipment's Modem/Fax Protection, please contact the Manager of Technical Support; Tripp Lite; 1111 W. 35th Street, Chicago, Illinois 60609; Phone: (773) 869-1234, for repair/warranty information. The telephone company may ask you to disconnect this equipment from the network until the problem has been corrected or you are sure the equipment is not malfunctioning. There are no repairs that can be made by the customer to the Modem/Fax Protection. This equipment may not be used on coin service provided by the telephone company. Connection to party lines is subject to state tariffs. (Contact your state public utility commission or corporation commission for information.)

6

Image 6
Contents Quick Installation Important Safety Instructions Quick Installation Set your UPS’s OFF on SwitchOptional Installation Test your UPSs battery charge SwitchesSilence the UPS alarm Basic OperationIndicator Lights Other UPS FeaturesService Storage & ServiceSpecifications StorageInstalación Rápida Advertencias sobre la conexión de equipos Advertencias sobre la ubicación del UPSAdvertencias sobre la conexión del UPS Advertencias sobre las bateríasUna toma de energía eléctrica Instalación RápidaConecte el no-break / sistema UPS a Regule el Interruptor OFF on encendido / apagadoOperación Básica InterruptoresLuces Indicadoras Arrancar en frío el no-break / sistema UPSAlmacenaje Almacenaje y ServicioOtras Características de este No-break / Sistema UPS ServicioEspecificaciones Todos LOS ModelosInstallation Rapide Mises en garde relatives au raccord de léquipement Mises en garde relatives à lemplacement du système UPSMises en garde relatives au raccord du système UPS Mises en garde relatives à la batterieInstallation Rapide Installation FacultativeCommutateurs Amortir l’alarme du système d’UPSOpération de Base Démarrage à Froid de votre système d’UPSVoyants de Signalisation Autres Dispositifs d’UPSEntreposage & Service CaracteristiquesEntreposage 93-155420000107102/00 REV.5.5/5.6