Tripp Lite SMART3000RMOD2U Power Module Replacement, Not shown Press “On” button until unit beeps

Page 12
Power Module Replacement

Power Module Replacement

The SMART3000RMOD2U features a hot-swappable power module. There is no manual bypass switch on the unit. However, when the bracket holding the power module in place is removed (see Step #3 below), the UPS will automatically switch to “BYPASS” mode, allowing the power module to be removed for maintenance, repair or replace- ment without disrupting power to connected loads. While the UPS is in “BYPASS” mode, connected equipment will receive unfiltered AC mains power, but the equipment will not receive battery power in the event of a blackout. NOTE: Do not turn off the UPS when removing the power module. Doing so will turn off the rear output. Do not remove the power module while operating from battery power.

Step 1: Remove front panel A .

Step 2: Disconnect battery connectors B .

Step 3: Remove the screws that hold power module in place. Remove smaller bracket covering bypass switch C .

Step 4: Remove power module D .

Step 5: Add new power module D .

Step 6: Replace the bypass switch bracket C and replace screws to secure power module to UPS.

Step 7: Connect battery connectors B . Attach connectors black-to-black and red-to- red.

Step 8: Replace front panel A .

Step 9 (Not shown): Press “On” button until unit beeps.

 

A

1

8

2

B

7

 

C

3

6

 

D

4

5

12

Image 12
Contents SmartPro Rackmount Intelligent, Line-Interactive UPS SystemIntroduction Maintenance WarningsBattery Warnings UPS Location WarningsFeatures Front Control PanelFeatures continued NOTE For additional information, see “Optional Installation” sectionRear Panel Mounting Mounting 4-Post Rackmount2-Post Telecom Mounting Mounting continued Mounting TowerQuick Installation 1 Plug the UPS into an outlet on a dedicated circuit2 Plug your equipment into the UPS 3 Turn the UPS OFFOptional Installation 3 External Battery Connection1 USB and Serial Communication Connection 2 EPO Port ConnectionBasic Operation Indicator Lights Front Panel“ON” Button “OFF/STANDBY” ButtonBasic Operation continued Load Level/Battery Capacity Indicator Lights Front Panel100% Load/Battery Bar LED 80% Load/Battery Bar LEDOther UPS Features Rear Panel Power Module Replacement Step 9 Not shown Press “On” button until unit beepsBattery Replacement Service StorageWarranty Warranty RegistrationFCC Radio/TV Interference Notice Regulatory Compliance Identification Numbers1111 W. 35th Street, Chicago, IL 60609 USA