Tripp Lite SMART3000RMOD2U owner manual Mounting 4-Post Rackmount, Post Telecom Mounting

Page 5
Mounting

Mounting

Mounting (4-Post Rackmount)

The UPS includes rackmount shelf kits for 4-post rackmounting. The user must determine the fitness of hardware and procedures before mounting. If hardware and procedures are not suitable for your application, contact the manufacturer of your rack or rack enclosure. The procedures described in this manual are for common rack and rack enclosure types and may not be appropriate for all applications.

WARNING! The UPS system is heavy. Use caution when lifting and mounting. User must properly stabilize the UPS when lifting and mount- ing.

1Connect the two segments of each shelf using the included screws and wing nuts A . Leave the screws slightly loose so that the shelves can be adjusted in the next step.

2Adjust each shelf to fit the rack, then mount them in the lowest

available space of the rack with the screws, nuts and washers provided B . Note that the support ledges should face inward. Tighten the wingnuts that connect the shelf segments.

3Attach mounting ears C to the front mounting holes of the UPS using the screws provided D . The ears should face forward.

4Using an assistant (if necessary), lift the UPS and slide it onto

the mounting shelves. Attach the UPS to the rack by inserting the appropriate hardware E through the mounting ears and into the rack rails.

1

 

 

 

2

A

B

B

 

 

 

B

B

A

 

 

3

 

 

 

 

D

 

 

C

4

E

2-Post (Telecom) Mounting

If you mount the SMART3000RMOD2U in a 2-post rack, it requires the addition of a Tripp Lite 2-Post Rackmount Installation Kit (Model: 2POSTRMKITWM, sold separately).

1Attach mounting ears A to the front mounting holes of your UPS B using the screws provided C . The ears should face backward.

2Using an assistant if necessary, lift your UPS and slide it onto

the mounting shelves. Attach your UPS to the rack by passing the screws, nuts and washers provided D through its mounting ears and into the rack rails.

1

B

A

C

2

 

D

 

5

Image 5
Contents Intelligent, Line-Interactive UPS System SmartPro RackmountMaintenance Warnings IntroductionBattery Warnings UPS Location WarningsFront Control Panel FeaturesRear Panel Features continuedNOTE For additional information, see “Optional Installation” section 2-Post Telecom Mounting MountingMounting 4-Post Rackmount Mounting Tower Mounting continued1 Plug the UPS into an outlet on a dedicated circuit Quick Installation2 Plug your equipment into the UPS 3 Turn the UPS OFF3 External Battery Connection Optional Installation1 USB and Serial Communication Connection 2 EPO Port ConnectionIndicator Lights Front Panel Basic Operation“ON” Button “OFF/STANDBY” ButtonLoad Level/Battery Capacity Indicator Lights Front Panel Basic Operation continued100% Load/Battery Bar LED 80% Load/Battery Bar LEDOther UPS Features Rear Panel Step 9 Not shown Press “On” button until unit beeps Power Module ReplacementBattery Replacement Storage ServiceWarranty Registration WarrantyFCC Radio/TV Interference Notice Regulatory Compliance Identification Numbers1111 W. 35th Street, Chicago, IL 60609 USA