Tripp Lite OMNISMART1400 warranty Leds Alarms & Switches, Surge / Noise Suppression, Physical

Page 3

Voltage regulation description

Overvoltage correction

Direct pass through

Brownout correction

Severe brownout correction

Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade 120V nominal output, without using battery power, during brownouts to 75V and overvoltages to 147V

Input voltages between 128 and 147V AC are reduced by 12%

Input voltages between 108 and 127V AC are passed on to connected equipment unchanged

Input voltages between 93 and 107V AC are boosted by 14%

Input voltages between 75 and 92V AC are boosted by 30%

LEDS ALARMS & SWITCHES

Front panel LEDs

Alarms

Switches

5 front panel LEDs indicate line power status, battery power status, battery low/replace status, voltage regulation operation and overload status

Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.

Includes 2 front panel switches — one main on/off power switch and one dual function "alarm cancel" / "self test" button

SURGE / NOISE SUPPRESSION

AC surge suppression

480 joules

 

 

AC suppression

Instantaneous

response time

 

 

 

Dataline suppression

-

 

 

EMI / RFI AC noise

Yes

suppression

 

 

 

PHYSICAL

 

Shipping weight (lbs)

40

 

 

Shipping weight (kg)

18.2

 

 

Unit weight (lbs)

36.4

 

 

Unit weight (kg)

16.5

 

 

Unit Dimensions

12.75 x 7.5 x 9

(HWD/in)

 

 

 

Unit Dimensions

32.4 x 19.1 x 22.9

(HWD/cm)

 

 

 

Material of

PVC

construction

 

 

 

Form factors

Tower

supported

 

 

 

Cooling method

Convection

 

 

Battery Access

Battery access door allows user replacement of UPS batteries. Hot-swappable battery replacement supported.

 

 

ENVIRONMENTAL

 

Relative Humidity

0 to 95%, non-condensing

 

 

Storage Temperature

+5 to +122 degrees Fahrenheit, -15 to +50 degrees Celsius

 

 

Operating

+32 to +104 degrees Fahrenheit, 0 to +40 degrees Celsius

Temperature

 

 

 

COMMUNICATIONS

 

Network monitoring

USB

port

 

 

 

Software and cabling

USB cabling included, PowerAlert software available for free download at www.tripplite.com

included

 

 

 

WatchDog

Compatible with Tripp Lite's Watchdog system service to restore operation to locked equipment through soft reboot of

compatibility

application / OS or hard power off/on reboot of connected equipment - ideal for unattended kiosk applications

 

 

LINE / BATTERY TRANSFER