Tripp Lite 120/208V owner manual Model SU30K3/3

Page 18

9. Specifications (continued)

Model: SU30K3/3

Input

Input Voltage

120/208V AC, 3ø, 4 Wire (plus ground), wye

 

 

Input Frequency

60 Hz ± 3 Hz

Voltage Correction Range

88-144/166-250V AC

 

 

Input Current (Per Phase, On-Line)

90A

Inrush Current

<300A

Power Factor (Full Load)

>0.95

 

 

Efficiency (Full Load/On-Line)

>89%

Circuit Breaker

100A (3p)

 

 

Input Bypass Circuit Breaker

100A (3p)

 

 

Output

 

 

 

VA

30000

Watts (Power Factor: 0.8)

24000

 

 

Waveform (On-Line)

Sinewave

 

 

Waveform (On-Battery)

Sinewave

Output Voltage (RMS)

120/208V AC, 3ø, 4 Wire (plus ground), wye

 

 

Output Frequency

60 Hz (± 0.1 Hz on battery)

 

 

Voltage Regulation

±2%

Max. Harmonic Distortion

<5%

(Non-Linear Full Load)

 

Overload Capabilities

102% (continuous), 102%~125% (1 min.),

 

125%~150% (30 sec.), 150% (2 sec.)

Short Circuit Capability

250A

 

 

Crest Factor

3:1

Battery

 

Battery Type

Sealed, Lead Acid, 240V DC, 9AH

 

 

Battery Pack Quantity

Three Packs (20 12V DC Batteries per pack)

 

 

Protection

Six UL-recognized 30A 600VDC rated cartridge

 

fuses (two per battery pack) and fuse block

 

(1 per battery pack)

Typical Backup Time (Half Load)

13 min. +

 

 

Typical Backup Time (Full Load)

5 min. +

Operation

 

On-Line Transfer Time

0 ms

(Line to Battery, Battery to Line)

 

Audible Noise (Full Load @ 1 meter)

<65 dBA

 

 

Indicators

 

Includes an LCD Display and LEDs (AC Line In, Bypass Line In, AC to DC, DC to AC, AC Output, Battery Back-Up, Bypass).

Communications

Includes an RS-232 DB9 female connector, an AS-400 DB9 female connector, a dry contact DB9 female connector and an accessory slot.

Connections

Input Terminal Block

100A

Output Terminal Block

100A

Physical Specifications

 

Unit Dimensions (H x W x D)

35.3 x 19.3 x 36 in.

 

 

Unit Weight

662 lb.

Shipping Dimensions (H x W x D)

43 x 28 x 44.5 in.

 

 

Shipping Weight

750 lb.

 

 

Model: SU30K3/3XR5

Input

Input Voltage

120/208V AC, 3ø, 4 Wire (plus ground), wye

 

 

Input Frequency

60 Hz ± 3 Hz

 

 

Voltage Correction Range

88-144/166-250V AC

Input Current (Per Phase, On-Line)

90A

 

 

Inrush Current

<300A

 

 

Power Factor (Full Load)

>0.95

Efficiency (Full Load/On-Line)

>89%

 

 

Circuit Breaker

100A (3p)

 

 

Input Bypass Circuit Breaker

100A (3p)

Output

 

VA

30000

 

 

Watts (Power Factor: 0.8)

24000

Waveform (On-Line)

Sinewave

Waveform (On-Battery)

Sinewave

 

 

Output Voltage (RMS)

120/208V AC, 3ø, 4 Wire (plus ground), wye

Output Frequency

60 Hz (± 0.1 Hz on battery)

 

 

Voltage Regulation

±2%

 

 

Max. Harmonic Distortion

<5%

(Non-Linear Full Load)

 

Overload Capabilities

102% (continuous), 102%~125% (1 min.),

 

125%~150% (30 sec.), 150% (2 sec.)

Short Circuit Capability

250A

Crest Factor

3:1

 

 

Battery

 

 

 

Battery Type

Sealed, Lead Acid, 240V DC, 9AH

Battery Pack Quantity

Five Packs (20 12V DC Batteries per pack)

Protection

Ten UL-recognized 30A 600VDC rated cartridge

 

fuses (two per battery pack) and fuse block

 

(1 per battery pack)

Typical Backup Time (Half Load)

25 min. +

 

 

Typical Backup Time (Full Load)

11 min. +

 

 

Operation

 

 

 

On-Line Transfer Time

0 ms

(Line to Battery, Battery to Line)

 

Audible Noise (Full Load @ 1 meter)

<65 dBA

Indicators

 

Includes an LCD Display and LEDs (AC Line In, Bypass Line In, AC to DC, DC to AC, AC Output, Battery Back-Up, Bypass).

Communications

Includes an RS-232 DB9 female connector, an AS-400 DB9 female connector, a dry contact DB9 female connector and an accessory slot.

Connections

Input Terminal Block

100A

 

 

Output Terminal Block

100A

 

 

Physical Specifications

 

 

 

Unit Dimensions (H x W x D)

48.5 x 19.3 x 36 in.

Unit Weight

935 lb.

 

 

Shipping Dimensions (H x W x D)

61.5 x 31 x 44.5

 

 

Shipping Weight

1152 lb.

+ Backup times are expandable with additional Battery Packs, sold separately. The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.

1111 W. 35th Street • Chicago, IL 60609 USA

(773) 869-1234 • www.tripplite.com

200901138 93-2624

18

Image 18
Contents Table of Contents Intelligent True On-Line UPS SystemsImportant Safety Warnings UPS Location WarningsControl Panels Front PanelBattery Access Panel Cover Removed Adding or Replacing Internal Batteries for detailsRear Panel CommunicationsInstallation Risk of Product Damage and Serious Personal InjuryOperation Normal Conditions Initial Battery ChargingSelf-Testing Turning the UPS OnOperation Special Conditions LCD Display Select ButtonOperation On Bypass-Voltage Out Of Range Operation Of Manual Bypass Switch Inverter On WarningsOperation Under Shutdown AS-400 Interface CommunicationsRS-232 Interface Dry Contact InterfaceBattery Packs are Heavy Remote Emergency Power Off EPODo not Remove Battery Sleeve Check Battery Pack Voltage BEFORE COMPLETING InstallationInternal Battery Pack Wiring Diagram Adding or Replacing Internal Batteries Terminals Fuse Replacement Warranty & Warranty Registration Observe Proper PolaritySpecifications Model SU20K3/3Model SU30K3/3