Tripp Lite 120/208V owner manual Specifications, Model SU20K3/3

Page 17

9. Specifications

Model: SU20K3/3

Input

Input Voltage

120/208V AC, 3ø, 4 Wire (plus ground), wye

 

 

Input Frequency

60 Hz ± 3 Hz

Voltage Correction Range

88-144/166-250V AC

 

 

Input Current (Per Phase, On-Line)

60A

Inrush Current

<300A

Power Factor (Full Load)

>0.95

 

 

Efficiency (Full Load/On-Line)

>89%

Circuit Breaker

100A (3p)

 

 

Input Bypass Circuit Breaker

100A (3p)

 

 

Output

 

 

 

VA

20000

Watts (Power Factor: 0.8)

16000

 

 

Waveform (On-Line)

Sinewave

 

 

Waveform (On-Battery)

Sinewave

Output Voltage (RMS)

120/208V AC, 3ø, 4 Wire (plus ground), wye

 

 

Output Frequency

60 Hz (± 0.1 Hz on battery)

 

 

Voltage Regulation

±2%

Max. Harmonic Distortion

<5%

(Non-Linear Full Load)

 

Overload Capabilities

102% (continuous), 102%~125% (1 min.),

 

125%~150% (30 sec.), 150% (2 sec.)

Short Circuit Capability

167A

 

 

Crest Factor

3:1

Battery

 

Battery Type

Sealed, Lead Acid, 240V DC, 9AH

 

 

Battery Pack Quantity

Two Packs (20 12V DC Batteries per pack)

 

 

Protection

Four UL-recognized 30A 600VDC rated cartridge

 

fuses (two per battery pack) and fuse block

 

(1 per battery pack)

Typical Backup Time (Half Load)

17 min. +

 

 

Typical Backup Time (Full Load)

5 min. +

Operation

 

On-Line Transfer Time

0 ms

(Line to Battery, Battery to Line)

 

Audible Noise (Full Load @ 1 meter)

<65 dBA

 

 

Indicators

 

Includes an LCD Display and LEDs (AC Line In, Bypass Line In, AC to DC, DC to AC, AC Output, Battery Back-Up, Bypass).

Communications

Includes an RS-232 DB9 female connector, an AS-400 DB9 female connector, a dry contact DB9 female connector and an accessory slot.

Connections

Input Terminal Block

100A

Output Terminal Block

100A

Physical Specifications

 

Unit Dimensions (H x W x D)

35.3 x 19.3 x 36 in.

 

 

Unit Weight

520 lb.

Shipping Dimensions (H x W x D)

43 x 28 x 44.5 in.

 

 

Shipping Weight

609 lb.

 

 

Model: SU20K3/3XR5

Input

Input Voltage

120/208V AC, 3ø, 4 Wire (plus ground), wye

 

 

Input Frequency

60 Hz ± 3 Hz

Voltage Correction Range

88-144/166-250V AC

 

 

Input Current (Per Phase, On-Line)

60A

Inrush Current

<300A

Power Factor (Full Load)

>0.95

 

 

Efficiency (Full Load/On-Line)

>89%

Circuit Breaker

100A (3p)

 

 

Input Bypass Circuit Breaker

100A (3p)

 

 

Output

 

 

 

VA

20000

Watts (Power Factor: 0.8)

16000

 

 

Waveform (On-Line)

Sinewave

 

 

Waveform (On-Battery)

Sinewave

Output Voltage (RMS)

120/208V AC, 3ø, 4 Wire (plus ground), wye

 

 

Output Frequency

60 Hz (± 0.1 Hz on battery)

 

 

Voltage Regulation

±2%

Max. Harmonic Distortion

<5%

(Non-Linear Full Load)

 

Overload Capabilities

102% (continuous), 102%~125% (1 min.),

 

125%~150% (30 sec.), 150% (2 sec.)

Short Circuit Capability

167A

 

 

Crest Factor

3:1

Battery

 

Battery Type

Sealed, Lead Acid, 240V DC, 9AH

 

 

Battery Pack Quantity

Five Packs (20 12V DC Batteries per pack)

 

 

Protection

Ten UL-recognized 30A 600VDC rated cartridge

 

fuses (two per battery pack) and fuse block

 

(1 per battery pack)

Typical Backup Time (Half Load)

42 min. +

 

 

Typical Backup Time (Full Load)

17 min. +

Operation

 

On-Line Transfer Time

0 ms

(Line to Battery, Battery to Line)

 

Audible Noise (Full Load @ 1 meter)

<65 dBA

 

 

Indicators

 

Includes an LCD Display and LEDs (AC Line In, Bypass Line In, AC to DC, DC to AC, AC Output, Battery Back-Up, Bypass).

Communications

Includes an RS-232 DB9 female connector, an AS-400 DB9 female connector, a dry contact DB9 female connector and an accessory slot.

Connections

Input Terminal Block

100A

Output Terminal Block

100A

Physical Specifications

 

Unit Dimensions (H x W x D)

48.5 x 19.3 x 36 in.

 

 

Unit Weight

935 lb.

Shipping Dimensions (H x W x D)

61.5 x 31 x 44.5

 

 

Shipping Weight

1152 lb.

 

 

+ Backup times are expandable with additional Battery Packs, sold separately. The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.

17

Image 17
Contents Intelligent True On-Line UPS Systems Table of ContentsUPS Location Warnings Important Safety WarningsFront Panel Control PanelsAdding or Replacing Internal Batteries for details Battery Access Panel Cover RemovedCommunications Rear PanelRisk of Product Damage and Serious Personal Injury InstallationSelf-Testing Initial Battery ChargingOperation Normal Conditions Turning the UPS OnOperation On Bypass-Voltage Out Of Range Operation Special ConditionsLCD Display Select Button Operation Under Shutdown Operation Of Manual Bypass SwitchInverter On Warnings RS-232 Interface CommunicationsAS-400 Interface Dry Contact InterfaceDo not Remove Battery Sleeve Remote Emergency Power Off EPOBattery Packs are Heavy Check Battery Pack Voltage BEFORE COMPLETING InstallationInternal Battery Pack Wiring Diagram Adding or Replacing Internal Batteries Terminals Fuse Replacement Observe Proper Polarity Warranty & Warranty RegistrationModel SU20K3/3 SpecificationsModel SU30K3/3