4.Operation (Normal Conditions) (continued)

4.4LCD Display Select Button

Momentarily press the “SELECT” button on the front panel to browse through different power readings on the LCD Display.

BYPASS OUTPUT

R:XXXV R: XXX.XV

S:XXXV S: XXX.XV

T:XXXV T: XXX.XV

(Bypass & Output Voltage)

Press "SELECT" Button

OUTPUT

LOAD

R: XXX%

XXX.XA

S: XXX%

XXX.XA

T: XXX%

XXX.XA

(Output Load & Current)

Press "SELECT" Button

MAINS

INVERTER

R: XXXV

R: XXX.XV

S: XXXV

S: XXX.XV

T: XXXV

T: XXX.XV

(Mains & Inverter Voltage)

Press "SELECT" Button

BYPASS: XX.X Hz

MAINS: XX.X Hz

OUTPUT: XX.X Hz

INVERTER: XX.X Hz

(Bypass, Mains, Output & Inverter Frequency)

Press "SELECT" Button

CHARGE FLOATING

CHARGER: XXX.XV

BATTERY: XXX.XV

BATTERY: XXX.X%

(Charger Mode, Charger/Battery Voltage & Battery Percentage)

Press "SELECT" Button

SN:

XXX

DC BUS:

XXV - XXV

TEMP:

XXX.X˚C

VERSION:

XXX

(Serial Number, DC BUS Voltage, Temperature & Firmware Version)

 

 

Press "SELECT" Button

 

 

 

 

ON:

UPS START

 

OFF:

UPS BYPASS

(Button Functions)

SEL:

UPS MESSAGE

ENT:

SET UPS

 

Press "SELECT" Button

5.Operation (Special Conditions)

5.1Operation On Bypass—Voltage Out Of Range

While in Bypass Mode, the UPS monitors the input voltage, which on Bypass equals the output voltage. If the output voltage passes out of an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying output power to its load. If power levels return to an acceptable level, the UPS resumes supplying power to the load, and its LCD reports that output voltage was too high or too low at one time, but has returned to nominal.

Bypass Voltage Condition

LCD Display Message

>15% Higher than Nominal

BYPASS HI NO O/P

 

 

>20% Lower than Nominal

BYPASS LO NO O/P

 

 

Was Too High, Now Nominal

BYPASS WAS HI

 

 

Was Too Low, Now Nominal

BYPASS WAS LO

 

 

8

Image 8
Contents Table of Contents Intelligent True On-Line UPS SystemsImportant Safety Warnings UPS Location WarningsControl Panels Front PanelBattery Access Panel Cover Removed Adding or Replacing Internal Batteries for detailsRear Panel CommunicationsInstallation Risk of Product Damage and Serious Personal InjuryInitial Battery Charging Self-TestingOperation Normal Conditions Turning the UPS OnOperation On Bypass-Voltage Out Of Range Operation Special ConditionsLCD Display Select Button Operation Under Shutdown Operation Of Manual Bypass SwitchInverter On Warnings Communications RS-232 InterfaceAS-400 Interface Dry Contact InterfaceRemote Emergency Power Off EPO Do not Remove Battery SleeveBattery Packs are Heavy Check Battery Pack Voltage BEFORE COMPLETING InstallationInternal Battery Pack Wiring Diagram Adding or Replacing Internal Batteries Terminals Fuse Replacement Warranty & Warranty Registration Observe Proper PolaritySpecifications Model SU20K3/3Model SU30K3/3