Configuration
UPS Settings
Start-up Settings
Configure these settings at initial
Note: During
Function | Factory Default Options | Description | |
|
|
|
|
Language | English | • English | The language for the display interface. |
|
| • French* | *Language options will vary by model. |
|
| • German* |
|
|
| • Spanish* |
|
|
| • Italian* |
|
|
| • Portuguese* |
|
|
|
|
|
Local Power | Good | • Good | Select the quality of input utility power. |
Quality |
| • Fair | • If Good is selected, the unit will go on battery |
|
| • Poor | power more often to provide the cleanest power |
|
|
| supply to the connected equipment. |
|
|
| • If Poor is selected, the UPS will tolerate more |
|
|
| fluctuations in power and will go on battery power |
|
|
| less often. |
|
|
| If unsure of the local power quality, select Good. |
|
|
|
|
Menu Type | Standard | Standard or | The advanced menus include all parameters. The |
|
| Advanced | Standard menus display a limited set of menus and |
|
|
| options. |
General Settings
Configure these settings at any time, using the display interface or APC PowerChute® software.
Function | Factory Default Options | Description |
High Transfer | 120 V: | • 127 Vac | |
Point | 127 Vac | • 130 Vac | |
|
|
| • 133 Vac |
|
|
| • 136 Vac |
|
|
|
|
| 208 | V: | • 225 Vac |
| 225 | Vac | • 229 Vac |
|
|
| • 233 Vac |
|
|
| • 237 Vac |
|
|
|
|
| 230 | V: | • 253 Vac |
| 253 | Vac | • 257 Vac |
|
|
| • 261 Vac |
|
|
| • 265 Vac |
To avoid unnecessary battery usage, set the transfer point higher if the utility voltage is chronically high and the connected equipment is known to work under this condition. The POWER QUALITY setting will automatically change this setting.
Note: Use the Advanced Menus to configure this setting.
7 |